2 AI-01 Module
2.3.1 Setting the Input Mode
2.3 AI-01 Module Settings
This section describes the items to be set using the MPE720 after connecting the AI-01 Module.
After connecting the AI-01 Module, use the following procedures to select the input mode, offset/gain, and self con-
figuration. If self configuration is performed after setting the input mode and offset/gain, the values will return to their
default values.
2.3.1 Setting the Input Mode
The AI-01 Module has three input modes
• Voltage Mode 1 (Input range: -10 V to +10 V)
• Voltage Mode 2 (Input range: 0 V to +10 V
• Current Mode (Input range: 0 mA to 20 mA)
The input mode for each channel must be selected both on the machine and in the MPE720 program. Both set-
tings must match.
For information on how to select the input mode on the machine, refer to 2.2.3 ( 2 ) AI-01 Module Connection
Example (CN1) on page 2-29.
In the MPE720 program ver. 5.31 or later, select the input mode for the channel to be used in the AI-01 Configuration
window.