Sdo 4Xdc 24V 0.5A - Fsoe Parameter Record Set; Fsoe Application Parameters - YASKAWA VIPA SLIO SDI Operating Manual

Safety digital i/o
Table of Contents

Advertisement

Product description
SDO 4xDC 24V 0.5A - FSoE Parameter record set > FSoE application parameters

2.9 SDO 4xDC 24V 0.5A - FSoE Parameter record set

2.9.1 FSoE application parameters

Record set 0x8000
Parameter
Sub-
Name
index
0
Subindex 000
1
Version identifier of the para-
metrization data structure
2
Module type identifier
3
Channel 0:
Wire break detection
4
Channel 1:
Wire break detection
5
Channel 0, 1:
Activation mode
6
Channel 0, 1:
Activation
1
7
Channel 2:
Wire break detection
8
Channel 3:
Wire break detection
9
Channel 2, 3:
Activation mode
10
Channel 2, 3:
1
Activation
50
This data record set is transmitted once via the FSoE mechanism when the FSoE master
system is started.
Description /
Range of values
0x0001: first version
Unique module identifier
Condition: Channel 0, 1 acti-
vation on "activated"
0: deactivated
1: activated
Bit is not security relevant.
Condition: Channel 0, 1 acti-
vation on "activated"
0: deactivated
1: activated
Bit is not security relevant.
Condition: Channel 0, 1 acti-
vation on "activated"
0: 1-channel
1: 2-channel
0: deactivated
1: activated
Condition: Channel 2, 3 acti-
vation on "activated"
0: deactivated
1: activated
Bit is not security relevant.
Condition: Channel 2, 3 acti-
vation on "activated"
0: deactivated
1: activated
Bit is not security relevant.
Condition: Channel 2, 3 acti-
vation on "activated"
0: 1-channel
1: 2-channel
0: deactivated
1: activated
Type
Bit
Offset
USINT
8
0
UINT16
16
16
UDINT
32
32
BOOL
1
64
BOOL
1
65
BOOL
1
66
BOOL
1
67
BOOL
1
68
BOOL
1
69
BOOL
1
70
BOOL
1
71
HB300 | SM-S | 02x-1SD10 | en | 20-02
VIPA System SLIO
Access
Default
ro
22
rw
1
rw
0x0C82AE00
rw
0
rw
0
rw
1
rw
1
rw
0
rw
0
rw
1
rw
1