Pin Assignment; Installation / Deinstallation - Wieland Samos Pro Compact SP-COP1 Instruction Manual

Main module of the modular safety controller
Hide thumbs Also See for Samos Pro Compact SP-COP1:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 7
3.3

Pin assignment

3.3.1
USB-Mini-socket
Standard-socket USB-Mini-B
3.3.2
RJ45-socket (only SP-COP2-ENx)
Standard-socket RJ45 (8P8C)
Transceiver: Auto MDI-X
3.3.3
Pin assignment SP-COP1
Module
3.3.4
Pin assignment SP-COP2x
Module
4

Installation / Deinstallation

4.1
Steps of installation of the modules
The system samos
cabinet with a protection degree of IP 54 or higher.
WARNING
WARNING
WARNING
WARNING
®
Within a system samos
PRO the controller SP-COPx is located on
the left-hand side of the modules, followed by one or two optional
gateways.
Pay attention to ESD-protective measures during the installation.
Otherwise the internal bus can be damaged.
The connection between the modules is realised by the integrated
S-BUS+ interface. Please take into account when exchanging a
module, that the samos
®
PRO modules must be pushed apart by
approx. 10 mm, before the corresponding module can be removed
from the standard rail.
Take suitable measures to ensure, that no foreign bodies get into
the plug openings.
Installation according to EN 50274
The modules have a housing width of 22.5 mm and are designed
for the installation on 35-mm-DIN-rails according to EN 60715.
Terminal
Description
A1
24 V power supply for
all modules, except
outputs
A2
GND of power supply
I1 - I20
Secure digital inputs
Q1 - Q4
Secure digital outputs
B1
24 V power-supply for
all outputs Q1...Q4
T1 - T4
Test signal outputs
Terminal
Description
A1
24 V power supply for
all modules, except
outputs
A2
GND of power supply
I1 - I16
Secure digital inputs
Q1 - Q4
Secure digital outputs
IQ1 - IQ4
Secure digital inputs
or outputs (configura-
tion via
®
samos
PLAN5+)
B1
24 V power supply for
outputs Q1 - Q4
B2
24 V power supply for
configuring outputs
IQ1 - IQ4
T1 - T4
Test signal outputs
®
PRO is designed for the use in a
4.1.1
Installing the SP-COP module
Push the release slide into the open position.
Tilt the module against the standard rail.
Observe the correct position of the shield contact. This shield
contact has to be connected properly to the DIN-rail.
Snap the module against the DIN-rail.
Push the release slide with a screwdriver against the Din rail, until
the release slide snaps into place with an audible click.
4.1.2
Installing extension modules
Tilt the module against the standard rail.
Observe the correct position of the shield contact. This shield
contact has to be connected properly to the DIN-rail.
Make sure that the module is firmly seated on the DIN-rail. Try to
withdraw the module from the DIN rail with light pressure. If the
module is fixedly connected to the DIN rail in this test, the assem-
bly is correct.
9 9 9 9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Samos pro compact sp-cop2

Table of Contents