Vertical Through-The-Roof Applications & Installation - Temco 36CDVRRN Installation Instructions And Homeowner's Manual

Builder direct vent
Table of Contents

Advertisement

CDV Series Direct Vent Gas Fireplace
Zero Clearance Sleeve
(if required)
Firestop
7" Pipe
24" (610mm)
Minimum*
BG402
Fig. 48 Below grade installation.
BG402a
Do not back fill around snorkel. A clearance
Top Vent
of at least 4" (102 mm) must be maintained
Below grade installation
between snorkel and the soil.
1/26/00 djt
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel.
Fasten brackets to wall first, then secure to snorkel
with self drilling #8 x 1/2 sheet metal screws. It will be
necessary to extend vent pipes out as far as protruding
wall face. (Fig. 49)
Foundation Recess
Recess Brackets
Watertight Seal
Around Pipe
Fig. 49 Snorkel installation, recessed foundation.
BG401
Snorkel
2/10/99 djt
24
Screws
7TDVSNORK
(Snorkel)
4" (102mm)
Clearance
Min.
Window
Well
Gravel
Drain
Foundation Wall
*A minimum of 24" (610mm) ver-
tical pipe must be installed when
using the 7TDVSNORK Kit.
*The 22" (559mm) vertical rise
(center to center) of the snorkel
may be included for calculationof
max. horizontal run.
Snorkel
Wall Screws
Sheet Metal
Screws
BG401
Vertical Through-the-Roof Applications
This Gas Fireplace has been approved for:
Vertical installations up to 40' (12 m) in height. Up
to a 10' (3 m) horizontal vent run can be installed
within the vent system using a maximum of two 90°
elbows. (Fig. 50)
Max. Height
40' (12m)
Min. Height
7���' (2.3m)
Fig. 50 Support straps for horizontal runs.
Up to two 45° elbows may be used within the
horizontal run. For each 45° elbow used on the
horizontal level the maximum horizontal length must
be reduced by 18" (457 mm).
Example: Maximum horizontal length
0 x 45° elbows = 10' 93 m)
1 x 45° elbows = 8¹⁄₂' (2.6 m)
2 x 45° elbows = 7' (2.1 m)
A minimum of an 8' (2.4 m) vertical rise.
Two sets of 45° elbows offsets within these vertical
installations. From 0 to a maximum of 8' (2.m) of
vent pipe can be used between elbows. (Fig. 51)
7DVCS must be used to support offsets. (Fig. 53)
This application will require that you first determine
the roof pitch and use the appropriate starter kit.
(Refer to Venting Components List)
The minimum height of the vent above the highest
point of penetration through the roof is 2' (610 mm).
(Fig. 55)
Max. 10' (3m)
Pipe Straps Every
3' (914mm)
FP1244
FP1244
through the roof
max/min dims
12/02
20010175