Braeburn Premier Series Detailed Installer Manual page 14

Up to 2 heat/1 cool heat pump 1 heat/1 cool conventional with humidity control
Hide thumbs Also See for Premier Series:
Table of Contents

Advertisement

26 Auto Changeover Dead Band [note 10] – When auto changeover mode is enabled in option 5 and
selected, the system automatically switches between heating and cooling when the room temperature
meets the normal criteria for either a heating or cooling call. There is a forced separation (dead band)
between the heating and cooling set points so that the systems do not work against each other. This
option selects the amount of this dead band in degrees with the default being 3° F.
27 Compressor Balance Point [notes 4, 11] – Locks out the use of the compressor heat stage when the
outside air temperature is less than the selected setting of 0° F to 15° F (-18° C to 10° C)
28 Auxiliary Heat Balance Point [notes 4, 11] – Locks out the use of the auxiliary heat stage when the
outside air temperature exceeds the selected setting of 70° F to 40° F (21° C to 4° C). NOTE: This
balance point overrides the fossil fuel compressor lockout in option 13. If this option is set to gas and
the outdoor temperature is over the auxiliary balance point, the compressor will remain on during a call
for auxiliary heat.
29 Heat Set Point Upper Limit – Selects the heating set point upper adjustment limit.
30 Cool Set Point Lower Limit [note 7] – Selects the cooling set point lower adjustment limit.
Installer Manual
Dehumidification
Over Cooling Limit
Dehumidification
not enabled
1˚ F (.5˚ C)
2˚ F (1.0˚ C)
3˚ F (1.5˚ C)
Allowable
Dead Band
2, 3, 4 or 5˚ F (1, 2 or 3˚ C)
3, 4 or 5˚ F (1, 2 or 3˚ C)
4 or 5˚ F (2 or 3˚ C)
5˚ F (3˚ C)
14