Braeburn Premier Series Detailed Installer Manual page 10

Up to 2 heat/1 cool heat pump 1 heat/1 cool conventional with humidity control
Hide thumbs Also See for Premier Series:
Table of Contents

Advertisement

No. Installer Setting
(
Notes follow this table)
9
1st Stage Fan Control
[note 3]
10
Emergency Heat]
[note 4]
Fan Control
11
Reversing Valve
[note 5]
(O/B Terminal)
12
Fossil Fuel
[note 4]
Backup Heat
Compressor Power Outage oF CPOP
13
[notes 4, 6]
Protection
14
AC Power Interrupt
Warning
[note 6]
15
Compressor Short
Cycle Protection
16
Residual Cooling
Fan Delay
[note 7]
17
Circulating Fan Lock
18
Adaptive Recovery
Mode (ARM™)
[note 8]
19
Indoor Remote Sensor
[note 9]
Control*
20
Lockout Security Level
21
Humidification
22
Auto Humidity Set
[note 11]
Point Limit
23
Dehumidification
24
Dehumidification Over
Cooling Limit
[note 12]
Dehumidification Terminal NI
25
[note 13]
(D) Output
26
Auto Changeover
Dead Band
[note 10]
Installer Manual
Factory
Default
HG FAN 1
HE EMER
REVO
AE AUX
AC oF MONR
5 CSCP
[note 7]
60 FAN
oF CIRC
oF REC
I SENS
2 LOCK
OFF
AUTO
OFF
1.0 LIM
3 BAND
Setting
Comments
Options
(More information follows this table)
HG FAN 1
Select for 1st stage Gas heating
HE FAN 1
Select for 1st stage Electric heating
HE EMER
Select for Electric Emergency Heat
HG EMER
Select for Gas Emergency Heat
REVO
Select for cool active Reversing Valve (O terminal)
REVB
Select for heat active Reversing Valve (B terminal)
AE AUX
Select for Electric Auxiliary heat (with compressor)
AG AUX
Select for Gas Auxiliary heat (without compressor)
oF CPOP
Disables Power Outage Lockout Delay
on CPOP
Enables Power Outage Lockout Delay
AC oF MONR Disables AC Power Interrupt Warning
AC on MONR Enables AC Power Interrupt Warning
5, 4, 3, 2 or
Select a compressor short cycle protection delay
0 CSCP
of 5, 4, 3, 2 or 0 minutes
90, 60, 30
Select a Residual Cooling Fan Delay of 90, 60,
or 0 FAN
30 or 0 seconds.
oF CIRC
Disables Circulating Fan Lock mode
on CIRC
Enables Circulating Fan Lock mode
oF REC
Disables Adaptive (early) Recovery mode
on REC
Enables Adaptive (early) Recovery mode
I SENS
Temperature is sensed from thermostat only.
E SENS
Temperature is sensed from remote sensor only.
A SENS
Temperature is combined with the thermostat
and the remote sensor.
2 LOCK
If locked – Complete lockout is enabled
1 LOCK
If locked – Partial lockout is enabled (SpeedBar
is still functional)
OFF
Disables Humidification
DEP
Enables Dependent Humidification
IND
Enables Independent Humidification
AUTO
Maximum humidity setpoint is limited based
on outdoor temperature.
MAN
Enables manual humidity control from thermostat.
OFF
Disables Dehumidification
DEP
Enables Dependent Dehumidification
IND
Enables Independent Dehumidification
1.0, 2.0 or
Select a dehumidification over cooling limit of
3.0 LIM
1.0°, 2.0° or 3.0° F (.5°, 1.0° or 1.5° C)
NI
Selects normally inactive relay (N/O)
NA
Selects normally active relay (N/C)
2, 3, 4 or 5
Select a Dead Band of 2°, 3°, 4° or 5˚ F
BAND
(1°, 2° or 3° C) for Auto Changeover mode.
10
®