Bionibal - Evinox ModuSat FS Series Installation Manual

Table of Contents

Advertisement

• Use suitable chemicals (such as BIONIBAL available from Evinox), which are suitable
for the materials and equipment used and that PREVENT/INHIBIT CORROSION.
Please note: If the completed installation includes boiler plant supplied by Evinox,
then only BIONIBAL, which is approved by Evinox, should be used in the primary
and secondary circuits.
Our technical personnel, who will visit the project during the course of the
installation and at its completion to arrange for its final commissioning and
calibration, do so to assist the contractor and install team. This is to deal with any
questions and queries; they do not perform the role of quality control or inspector of the
installation or provide approval for the works carried out. The systems compliance with the
consultant's requirements and current standards and legislation remains the exclusive
responsibility of the installer / M&E contractor and comments provided by Evinox are for
guidance & advice only.
4.4

Bionibal

BIONIBAL corrosion inhibitor is approved by Evinox and is a requirement in installations
that incorporate our boiler plant. Thorough research shows that Bionibal protects your
installation in 4 key ways:
• FIRST LEVEL - corrosion inhibition and prevention of rust build up.
• SECOND LEVEL - acidic component that stops bacteria and algae growth, particularly
useful in under floor heating working at low temperatures.
• THIRD LEVEL - prevents the adherence of suspended particles such as tartar, keeping
the surfaces clean (pumps, valves, heat meters, etc.).
• FOURTH LEVEL - provides traceability to enable the dosage to be fully monitored and
guarantee the best protection level. It also provides a trace element to enable any
leaks to be quickly identified.
Electrolytic corrosion prevention, in a circuit employing different metals.
IT IS ADVISABLE to ADD a suitable approved corrosion inhibitor before the
system is put in operation.
Bionibal dosage and use (If used & when required if Evinox boiler plant is installed)
NEW INSTALLATIONS:
Fill the circuit with water and check for leaks
any installation residuals (if necessary clean it with an appropriate product and
make sure that the circuit is well rinsed).
Once the circuit is well cleaned, fill it with water again and add BIONIBAL
according to the dosage indicated.
EXISTING INSTALLATIONS:
Because BIONIBAL doesn't dissolve existing limes and other residuals
accumulated over the years, proceed with empting the circuit and perform a
thorough cleaning process of it. Use accredited companies for this work.
Once the circuit is well cleaned, fill it with water again and add BIONIBAL
according to the dosage indicated below:
IMPORTANT WARNING
Bionibal must only be put in a thoroughly clean installation that has been fully checked. It
is therefore imperative to fill the entire system one or more times with clean water and
Empty the circuit in order to discard
.
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents