Engineering Information (Continued):
Operator Interface Panel (OIP) (Continued):
Configuration Menu:
The configuration menu contains a number of internal calibration settings. A password must be entered
in order to access this menu. The factory default engineering password is 1234.
Configuration Menu
Information Panel
ENGINEERING
PASSWORD
HMI SOFTWARE
PLC SOFTWARE
REMOTE HIGH
REMOTE LOW
REMOTE SETPOINT
INLET TC OFFSET
PROCESS DEVIATION
INLET TC READING
M-43-25
Revision - Date 03-01-04-18
Figure 14: Configuration Menu (2 Screens)
Displays the current engineering password. Press the password
value to bring up a keypad to change the password.
The factory default password is 1234.
Displays the HMI software version installed in this unit.
Displays the PLC software version installed in this unit.
Upper scaling input value for the remote setpoint setting.
setting corresponds to a 20mA input signal from the remote setpoint
input.
Lower scaling input value for the remote setpoint setting.
setting corresponds to a 4mA input signal from the remote setpoint
input.
Displays the remote setpoint value from the remote device.
Inlet temperature sensor offset value.
Press the inlet TC offset value to bring up a keypad to change the
setting.
Displays the +/- range for the process outlet temperature. When the
process outlet temperature deviates from this range, the process
deviation alarm is activated. Press the process deviation value to
bring up a keypad to change this setting.
Displays the value of the inlet temperature sensor.
23
Description
The range is -10 to +10.
LUF-Series Lufran Manual