Table 4-10 Technical Specifications Of The Ground Cable; Table 4-11 Technical Specifications Of The Ot Terminal - Raisecom ISCOM6800 Hardware Description

Table of Contents

Advertisement

Raisecom
ISCOM6800 (A)Hardware Description

Table 4-10 Technical specifications of the ground cable

Model (recommended)
Standard
Conducting wire
OT terminal
Stripped end
Insulating sheath
Welding technology
Error in length of
conducting wire
The letter D in the model indicates the length, which can be customized. For example,
if the customer requires 4-meter cables, they are named PIL-ground cable-RNB22-
6S/stripped-16mm2-4m/RoHS.
Table 4-11 lists technical specifications of the OT terminal.

Table 4-11 Technical specifications of the OT terminal

Model
Standard
Specifications
Cross-sectional area of
conducting wire
The ISCOM6800 is delivered without the ground cable. If required, prepare or
make ground cables on site.
The ground cable cannot be longer than 30 m and should be as short as possible;
otherwise, a grounding bar should be used.
Parameter
POL-ground cable-RNB22-6S/stripped-16mm2-D/RoHS
Comply with the UL standard and meet RoHS requirements.
Yellow/Green copper-core conducting wire 5 AWG (16
mm
RNB22-6S cold pressed terminal
10 mm long and plated with tin
Flame-retardant heat-shrink sheath (black)
The conducting wire and OT terminals adopt solderless
pressed connection.
± 5 mm
Parameter
Protective grounding round pressed terminal
RNB22-6S
5–4 AWG (16–25 mm
Raisecom Proprietary and Confidential
Copyright © Raisecom Technology Co., Ltd.
2
)
Inner diameter of soldering lug: 3.25 mm
Outer diameter of soldering lug: ≤ 6.1 mm
2
)
Description
Description
4 Cables
46