INSTALL ALL VENTS AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER!
When your Pellet Stove Room Heater is being installed on a combustible floor it is mandatory that a 1/2"
(13mm) thick non‐combustible hearth pad be installed under the heater. The non‐combustible hearth
pad must extend at least 6" beyond the fuel loading and ash removal openings and at least the depth of
the heater plus 6 inches (152mm) out in front of the heater. This applies to both freestanding heaters
and insert heaters.
CLEARANCES TO COMBUSTIBLES
USA 6"
CANADA 8"
USA 6"
CANADA 8"