I N S T A L L A T I O N
1.
The installation must be done by a qualified and licenced electrician
according the local legislation.
2.
The electrical installation must be free of power during the entire
installation period.
3.
Since this Charging Unit uses circuits that reference to ground, no
Megging must be done after connecting to power.
4.
Wiring and protection:
Version
32A / 1 Phase
3G6,00mm
32A / 3 Phase
5G6,00mm
* For cable length upto 25m
PLEASE NOTE: All charges include an AC (> 30mA) and
5.
Open bottom cover of the
Charge Station (5 screws –
see picture). Carefully brake
out required cable opening
for incoming power cable
and charge cable.
Use supplied M25 cable
gland to fix power cable
from the bottom.
Use supplied grommet to fix
power cable from the back.
Use supplied M25 cable gland
to fix charge cable.
6.
Use 4 wood screws M4,5x35mm to mount Charging Station on the wall.
The Charging Station should be installed between 0,80m and 1,20m from
bottom to the ground.
Wiring *
Mains Circuit Breaker
2
2
DC (> 6mA) residual-current-det ection.
Always place a type A RCD and the MCB (or
combination unit) in the electrical cabinet.
Residual Current Device
(MCB)
Fixed cable
(RCD)
30mA, Type A
Outlet
SMART BOX / Version: EV050
5