Fiber network module FN2006 / FN2007
1
Pin assignments
1.4.3
12
Siemens Industry, Inc.
Building Technologies Division
Sockets for FCnet/C-WEB circuits (7, 8)
The 3-pole connectors for the FCnet/C-WEB connection are supplied with the fiber
network module.
The total cable length of the electrical FCnet/C-WEB connections (copper cable) in
the optical network must not exceed 3300 ft.
Connection bush A1/B1
Pin
Designation
3
B1
2
NC
1
A1
Admissible cable cross-section: 16...28 AWG
Connection bush A2/B2 (7, 8)
Pin
Designation
3
B2
2
NC
1
A2
Admissible cable cross-section: 16...28 AWG
Description
FCnet/C-WEB circuit 1 (-)
Do not use
FCnet/C-WEB circuit 1 (+)
Description
FCnet/C-WEB circuit 2 (-)
Do not use
FCnet/C-WEB circuit 2 (+)