1.4.2
Siemens Industry, Inc.
Building Technologies Division
Power supply sockets (4, 6)
The 5-pole connectors for the power supply are supplied with the fiber network module.
Pin
Designation
1
DC 24 V+
2
DC 24 V-
3
COM
4
NO
5
NC
Admissible cable cross-section: 16...28 AWG
When installing in the fire control panel, the power supply does not have to be
supervised or routed redundantly.
The supply line for a remote network module must be shielded.
In the event of an error, relay contacts COM and NC are connected.
1 2 3 4 5
+ -
C NO NC
Terminal Plug
without housing
Connector power A (B)
Fiber network module FN2006 / FN2007
Description
Supply input + of DC 24 V AUX from periphery board
Supply input - of DC 24 V AUX from periphery board
Common contact
Normally open
Normally closed
Connector
Cover cap (open)
360º shielding
1
Pin assignments
Terminal Plug
with housing
11
A6V10315048_b_en_US