12� Technical specifications
Dimensions W × H × D
80 × 80 × 50 mm
Supply voltage
220-240 ~V / 50/60 HZ
Sensor system
Passive infrared (IR) / high-frequency (HF)
Sensor system
IR max. 20 m (tangential) / max. 4 m (radial) /
HF max. 8 m
Angle of coverage
180°
Light-level setting
10-1000 lux, ∞ / daylight
Time setting
30 sec - 30 min, Time setting, IQ mode (automatic
adjustment to the usage profile)
Mounting height
1.1 m
DALI output 1
2-core control cable, single-master
controller/broadcast application
Guaranteed supply current
Maximum supply current
DALI output 2
2-core control cable, single-master
controller/broadcast application
Guaranteed supply current
Maximum supply current
Twilight setting
2-1000 lux
IP rating
IP20
Temperature range
0°C to 40°C
* At extreme angles, the reach of the HF 180 is extensively determined by local
conditions.
5
3
Y E A R
Y E A R
MANUFACTURER'S
MANUFACTURER'S
WARRANTY
WARRANTY
*
24 mA
250 mA
24 mA
250 mA
- 30 -
13� Troubleshooting
Malfunction
Cause
Light does not switch ON n No supply voltage
n Lux setting too low
n No motion being
detected
Light does not switch OFF n Lux setting too high
n Stay-ON time still
effective
n Interfering heat sources:
e.g. fan heater, open
doors and windows,
pets, light bulb / halo-
gen floodlight, moving
objects
Sensor switches OFF
n Stay-ON time too short
despite persons being
n Lux setting too low
present
Sensor does not switch
n Stay-ON time too long
OFF quickly enough
Sensor does not switch
n Reach is reduced when
ON quickly enough when
approached from the
approached from the front
front
Sensor does not switch
n Lux setting too low
ON when persons are
present despite it being
dark
Switch not working
n Switch deactivated?
Remedy
n Check supply voltage
n Slowly increase lux set-
ting until light switches
ON
n Ensure unobstructed
sensor vision
n Check detection zone
n Reduce lux setting
n Wait until stay-ON time
elapses; reduce stay-
ON time if necessary
n Use stickers to mask
out stationary sources
of interference
n Increase stay-ON time
n Change lux setting
n Reduce stay-ON time
n Install additional sensors
n Reduce distance
between two sensors
n Sensor deactivated by
switch?
n Semi-automatic mode?
n Increase lux setting
n Check DIP switch 3
setting
- 31 -