Supply Wiring

The LC6000 controller is powered by 120, 208 or 230 volts from the shelter. Field-supplied supply wiring should
be minimum 16 gauge, maximum 14 gauge (see Figure 26). A reliable earth ground must be connected in addition
to any grounding from conduit. Grounding bolts and nuts are included with the controller for this purpose; a 2 hole
grounding lug must be field supplied. Install as shown in Figure 27. Failing to ground the controller box properly
could result in damage to the equipment.
2
1
120
208V
VAC
VAC
Input
Input
(L1)
(L1)
FIGURE 26
LC6000 Controller Circuit Install
3
4
5
230V
Power
VAC
Input
Input
Common
(L1)
(L2 or N)
FIGURE 27
Controller Grounding Posts
A reliable earth ground must be connected in addition to any
grounding from conduit. Attach earth ground to side of controller box
using bolts and nuts supplied with controller and field-supplied 2
hole grounding lug. Failing to ground the controller box properly could
result in damage to the equipment.
Power
Input
8
9
10
11
6
7
Ground
12
13
16
18
14
15
17
Manual 2100-705B
Page
29 of 43
20
21
19