Bard 357-93-E Specifications

Bard wl series wall mount air conditioners with left side control panel model 357-93-e

Advertisement

Quick Links

WL - SERIES
1.5 to 6 Ton (18,300 to 67,000 Btuh)
Left Side Control Panel
The Bard Wall-Mount Air Conditioner with Left Side Control Panel is
designed to provide complete service access (i.e. compressor, electric heat
strip and electrical controls) when two units are mounted side by side with
minimal space between. The left side unit is the ideal product for
telecommunication and over-the-road medical and communication vans
requiring two wall-mount air conditioners be mounted side by side by using
a WL (left side access) unit and a WA (right side access) unit on the same
building. Factory or field installed accessories are also available to meet
specific job requirements.
Engineered Features
Aluminum Finned Copper Coils:
Grooved tubing and enhanced
louvered fin for maximum heat transfer
and energy efficiency.
Twin Blowers:
Move air quietly. Most models feature
multispeed blower motors providing
airflow adjustment for high and low
static operation. Motor overload
protection is standard on all models.
Air Conditioner Compressor:
Reciprocating compressors with
crankcase heater and dual discharge
muffler are standard on 1.5 and 2 ton
models.
Scroll Compressors eliminate need for
crankcase heater. Standard on 2.5 to
5 ton, and available on 2 ton models.
Phase Rotation Monitor:
Standard on all 3 phase scroll
compressors. Protects against reverse
rotation if power supply is not properly
connected. Not required on
reciprocating compressors.
Galvanized 20 Gauge Zinc Coated
Steel Cabinet:
Cleaned, rinsed, sealed and dried
before the polyurethane primer is
applied. The cabinet is handsomely
finished with a baked on textured
enamel, which allows it to withstand
1000 hours of salt spray tests per
ASTM B117-03.
Electrical Components:
Are easily accessible for routine
inspection and maintenance through a
left side, service panel opening.
Features a lockable, hinged access
cover to the circuit breaker or pull
disconnect switch.
Electric Heat Strips:
Features an automatic limit and
thermal cut-off safety control. Heater
packages can be factory installed for
all 1.5 through 6 ton models.
• Complies with efficiency requirements of ASHRAE/IESNA 90.1-2004.
• Certified to ARI Standard 390-2003 for SPVU (Single Package Vertical Units).
• Commercial Product - Not intended for Residential application.
THE WALL-MOUNT™ AIR CONDITIONERS - WL (60HZ)
with LEFT SIDE CONTROL PANEL
Refrigerant 22
One Inch, Disposable Air Filters:
Are standard equipment. Optional one
inch washable filters available and filter
racks permit the addition of 2" pleated
filter. Factory or field installed.
Built-in Circuit Breakers:
Standard on all single (230/208 volt) and
three phase (230/208 volt) equipment.
Toggle disconnects are standard on all
three phase (460 volt) equipment.
Slope Top:
Standard feature for water run-off.
Top Rain Flashing:
Standard feature on all models.
Full Length Mounting Brackets:
Built into cabinet for improved
appearance and easy installation.
NOTE: Bottom mounting bracket
included to assist in installation.
Auto-Reset High Pressure Switch:
Built-in lock-out circuit resets from the
room thermostat. Provides commercial
quality protection to the compressor.
Auto-Reset Low Pressure Switch:
Built-in lock-out circuit and low pressure
timed bypass circuit. Resets from room
thermostat.
Compressor Control Module:
Built-in off-delay timer adjustable from 30
second to 5-minutes. 2-minute on-delay
if power interrupt. 120-second bypass for
low pressure control, and both soft and
manual lockouts for high and low
pressure controls. Alarm output for alarm
relay.
Low Ambient Control:
Permits cooling operation down to 0°F
outdoor ambient.
Alarm Relay:
Dry contacts for remote alarm capability
on manual high or low pressure controls.
60Hz
Ventilation System Packages
All packages are designed
to meet your specific
ventilation requirements
utilizing one of five
ventilation options for the
product. The ventilation
package is mounted within
the unit eliminating the need
for an exterior mounted
hood or damper assembly
on the unit. All assemblies
can be factory installed,
installed in the field at time
of installation or as a retrofit
system after installation.
MEA# 357-93-E
Standard - Barometric
Fresh Air Damper
Optional - Motorized
Fresh Air Damper
Optional - Blank off Plate
Optional - Commercial
Room Ventilator with Exhaust
• CRV - Spring Return
• CRVP - Power Return
Optional - Economizer w/Exhaust
Form No.
S3279-206
Supersedes
S3279-106
Page
1 of 12

Advertisement

loading
Need help?

Need help?

Do you have a question about the 357-93-E and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bard 357-93-E

  • Page 1 1.5 to 6 Ton (18,300 to 67,000 Btuh) Left Side Control Panel The Bard Wall-Mount Air Conditioner with Left Side Control Panel is designed to provide complete service access (i.e. compressor, electric heat strip and electrical controls) when two units are mounted side by side with minimal space between.
  • Page 2 Capacity and Efficiency Ratings n i l y t i 1 Capacity is certified in accordance with ARI Standard 390-2003 and tested in accordance with ARI Standard 210/240-2003. 2 EER = Energy Efficiency Ratio and is certified in accordance with ARI Standard 390-2003. SEER = Seasonal Energy Efficiency Ratio and is tested in accordance with ARI Standard 210/240-2003.
  • Page 3 Ventilation System Packages Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory, or field-installed at a later date.
  • Page 4: Electrical Specifications

    Electrical Specifications s t l s t i 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity”...
  • Page 5 Commercial Room Ventilator Performance Data - CRV-2 WL18, WL24 & WL25 TOTAL AND VENTILATION AIRFLOW 1100 1000 Vent Position Total Air 0 ESP Total Air .15 ESP Total Air .3 ESP Vent Air 0 ESP Vent Air .15 ESP Vent Air .3 ESP Form No.
  • Page 6 Commercial Room Ventilator Performance Data - CRVS-3 and CRVP-3 WL30 & WL37 HIGH SPEED TOTAL AND VENTILATION AIRFLOW 1200 1100 1000 WL30 & WL37 LOW SPEED TOTAL AND VENTILATION AIRFLOW 1000 Form No. S3279-206 Supersedes S3279-106 Page 6 of 12 Vent Position Vent Position Total Air 0 ESP...
  • Page 7 Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5 WL42 & WL48 HIGH SPEED TOTAL AND VENTILATION AIRFLOW 2100 2000 1900 1800 1700 1600 1500 1400 1300 1200 1100 1000 WL42 & WL48 LOW SPEED TOTAL AND VENTILATION AIRFLOW 1700 1600 1500 1400...
  • Page 8 Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5 WL60 & WL70 HIGH SPEED TOTAL AND VENTILATION AIRFLOW 2200 2100 2000 1900 1800 1700 1600 1500 1400 1300 1200 1100 1000 WL60 & WL70 LOW SPEED TOTAL AND VENTILATION AIRFLOW 1600 1500 1400...
  • Page 9 Indoor Blower Performance - CFM at 230 or 460 Volts / y r l i o / y r Above data is with 1" standard disposable filter and 1" washable filter. For optional 2" pleated filter - reduce ESP by .15 in. See installation instructions for maximum ESP information on various KW application.
  • Page 10 Cooling Application Data - Outdoor Temperature 1 n i l y t i l a t n i l n i l l a t n i l n i l l a t n i l n i l l a t n i l n i l...
  • Page 11 NOTE: For side by side installation of two (2) WL models there must be 20" between units. This can be reduced to 15" by using a WL model (left side compressor and controls) for the left unit and WA (right side compressor and controls) for right unit. BACK VIEW 1 21.00 inches on model WL701 "...
  • Page 12 "V" control module should be ordered in conjunction with direct digital controller (DDC) model TCS22. Refer to DDC specification sheet S3280 for more information. BARD MANUFACTURING CO. BRYAN, OHIO 43506 www.bardhvac.com Form No.