For proper operation, the remote indoor temperature/humidity sensor (and any additional sensors) must be
configured properly with the controller as shown in Step 2 on page 20. An additional remote indoor temperature-
only sensor can be purchased and installed in Zone 1. If the site in which the LC6000 controller will be used has
more than one zone (maximum three zones per LC6000), additional remote temperature/humidity sensors (one per
zone) will need to be purchased and installed in the additional zones. All installed sensors must be enabled in the
controller menu (see Configure Sensors beginning on page 35).
Additional Remote Indoor Temperature and Temperature/Humidity Sensor Installation
One additional temperature sensor can be added to Zone 1 and additional temperature/humidity sensors may be
added to Zones 2 and 3 (one per zone). Be sure the sensors are connected to the proper terminals on the terminal
block and sensor as listed below.
Zone 1:
Optional Remote
Temperature Sensor
Terminals 20 & 21*
Zone 2:
Optional Remote
Temperature/Humidity Sensor
Terminals 26, 27, 14, 15 & 23
IMPORTANT: Note jumper
position in Figure 16
Zone 3:
Optional Remote
Temperature/Humidity Sensor
Terminals 28, 29, 16, 17 & 24
IMPORTANT: Note jumper
position in Figure 16
Zones 2 and 3 can also use temperature-only sensors in place of the temperature/humidity sensors. Zone 2 will connect
to TB# 26 and 27. Zone 3 will connect to TB# 28 and 29. The wire connections for the temperature-only sensors are not
polarity sensitive.
FIGURE 17
Wire
TB#
Mark
20
B7
Indoor Remote Sensor (Zone 1 – optional)
21
GND
Ground
* The two wire connections for the optional remote temperature sensor
are not polarity sensitive.
Wire
TB#

Sensor

Mark
26
B8
NTC OUT Indoor Remote Sensor (Zone 2)
27
GND
NTC OUT Ground
14
B3
OUT H
15
GND
M (GO)
23
+VDC
+ (G)
Wire
TB#
Sensor
Mark
28
B9
NTC OUT Indoor Remote Sensor (Zone 3)
29
GND
NTC OUT Ground
16
B4
OUT H
17
GND
M (GO)
24
+VDC
+ (G)
Description
Description
Remote Indoor Humidity Sensor: 0-1 VDC (Zone 2)
Ground
Power for B3
Description
Remote Indoor Humidity Sensor: 0-1 VDC (Zone 3)
Ground
Power for B4
Manual 2100-705B
Page
21 of 43