SYSTEM SET UP

NOTE: Screenshots shown in this manual reflect
default settings (when applicable).
The LC6000 controller and TEC-EYE hand-held
diagnostic tool will both be used to set up the Bard
free cooling system (the TEC-EYE is only used to set
up the wall-mount units). If installing a single MEGA-
TEC wall-mount unit with a PGDx or PGD stand-alone
display, refer to PGD manual 2100-734 or PGDx
manual 2100-740 for information on setting up a
stand-alone display for single unit operation.
TABLE 4
LC6000/TEC-EYE Passwords (Defaults)
User
Technician
Engineer
Use UP or DOWN keys and ENTER key to enter password

TEC-EYE Hand-Held Diagnostic Tool

The microprocessor control used in the MEGA-TEC
wall-mount air conditioners allows for complete control
and monitoring through the use of the provided TEC-
EYE hand-held monitor.
The menu driven interface provides users the ability
to scroll through two menu levels: Quick Menu and
TEC-EYE (Bard P/N 8301-059) Display and Interface (Status Screen Shown)
ALARM KEY
MENU KEY
ESCAPE KEY
ALARM KEY
Allows viewing of active alarms
Silences audible alarms
Resets active alarms
MENU KEY
Allows entry to Main Menu
ESCAPE KEY
Returns to previous menu level
Cancels a changed entry
Manual 2100-705B
Page
32 of 43
Main Menu. The menus permit the user to easily view,
control and configure the unit. See the latest version
of MEGA-TEC Service Manual 2100-671 for more
information on using the TEC-EYE.
The TEC-EYE connects to the wall-mount unit control
board via an RJ11 modular connector as shown in
Figure 29.
When not being used, the TEC-EYE hand-held diagnostic
tool should be stored inside or near the LC6000
controller. Do not let the TEC-EYE leave the shelter.
2000
1313
9254
FIGURE 30
UP KEY
Steps to next screen in the display menu
Changes (increases) the value of a modifiable field
ENTER KEY
Accepts current value of a modifiable field
Advances cursor
DOWN KEY
Steps back to previous screen in the display menu
Changes (decreases) the value of a modifiable field
FIGURE 29
TEC-EYE Connection to Unit Control
Modular Connector for TEC-EYE
Hand-Held Diagnostic Tool