Air Conditioning System
This Bard air conditioning system is comprised of
MEGA-TEC wall-mounted air conditioners matched
with an LC6000 supervisory controller or Bard PGD/
PGDx stand-alone display. If only one wall-mounted
air conditioner is being used, it can be matched with
either the LC6000 supervisory controller or stand-alone
controller (see Single Unit Operation on page 3 for
information on the PGD and PGDx). If more than one
wall mount is installed, the LC6000 controller must
be matched with the air conditioning units. The wall-
mount units are specifically engineered for telecom/
motor control center rooms.
LC6000-200 Series Controller and Accessories Included with Controller
(1) LC6000 Programmable Logic
Controller
Outside Air
Temperature/Humidity Sensor
Bard P/N 8301-090
One remote temperature/humidity sensor is included with the LC6000 controller. If the site in which the LC6000
1
controller will be used has more than one zone (maximum three zones), additional remote temperature/humidity
sensors (one sensor per zone) will need to be purchased and installed in the additional zones. One additional
temperature-only sensor (Bard P/N 8301-058) may also be used in Zone 1 but will also need to be purchased
separately. Additional temperature/humidity sensors require field-supplied 5-wire 18 gauge shielded cable.
Temperature-only sensors require field-supplied 2-wire 18 gauge shielded cable.
NOTE: The LC6000 supervisory controller or stand-
Controller
LC6000 controller and accessories shown below.
+
Optional Sensors:
Remote
Temperature/Humidity Sensor
Bard P/N 8403-079

GENERAL INFORMATION

alone display and MEGA-TEC wall-mount units
are designed specifically to work together.
The controller or stand-alone display cannot
run other brands of systems, nor can other
controllers run the MEGA-TEC wall-mount units.
They are a complete system, and must be used
together.
(1) TEC-EYE
Hand-Held Diagnostic Tool
TM
Bard P/N 8301-059
(1) Remote Temperature/Humidity Sensor
Bard P/N 8403-079
(1) 35' 5-Wire 18 Gauge Shielded Cable
(2) Communication EMI Filters
Bard P/N 8301-055
Temperature Only Sensor
1
Bard P/N 8301-058
1
Remote
Manual 2100-705B
Page
3 of 43