Y05/YL5 INSTALLATION INSTRUCTIONS
General Description: This application should be installed and used as recommended by the National Fire Protection
Association standards and practices.
The Installer should be familiar with these requirements together with any local codes or special requirements of the local
Fire Authority having jurisdiction.
The alarm sounders are intended for connection to the output alarm circuit of a UL listed fire alarm control panel only. All
alarms are compatible with DC line status monitoring. The alarm sounders are suitable for outdoor use (-35ºC to +66ºC).
Installation procedures must confirm to appropriate agency requirements including but not limited to the following:-
NFPA72E, NEC ART.760 ET.AL., CAN/ULC-S524-M86, CEC PART 1 SEC 32
Installation: The sounder can be affixed to most surfaces using screws through the external mounting lugs or by drilling
internal fixing holes. A 20mm gland entry is provided for the supply cable. The cable and gland must be fitted in accordance
with the national and local regulations. It is not necessary to earth the sounder circuitry but earth tags should be used if earth
continuity of conduit or cable sheathing needs to be maintained.
Supply input: Ensure that the supply is correct for the voltage rating of the sounder or combined sounder strobe being
installed. Ensure the supply is OFF before making any connection and wire only in accordance with the terminal label detail.
Sound selection: Ensure the supply is OFF before proceeding. All dc and ac units have selectable alarm sounds (see table
below for details) and are selectable by means of a 5 way dil switch SW1. A second sound is made available upon the
application of a third wire connected to terminal TB1/3 as shown in Fig. 1 while still connected to terminal TB1/2. Alternatively
1st and 2nd stage sound signals can be generated by supply reversal (FOR DC UNITS ONLY) see Fig. 2. Independent
second stage sound is available by using SW2 (OPTIONAL- only fitted with orders).
WARNING - Loud alarm sound. Wear ear defenders when testing, installing and commissioning.
SOUND SELECTION TABLE
First Stage Sound
frequency
Hertz
1 Alternate two-tone
800-1000
2 Alternate two-tone
2500-3100
3 Alternate fast two-tone
800-1000
4 Alternate fast two-tone
2500-3100
5 Alternate two-tone
440-554
6 Alternate two-tone
430-470
7 Alternate v.fast two-tone 800-1000
8 Alternate v.fast two-tone 2500-3200
9 Alternate two-tone
440-554
10 Continuous note
700
11 Continuous note
1000
12 Continuous note
1000
13 Continuous note
2300
14 Continuous note
440
15 Interrupted tone
1000
16 Interrupted tone
420
17 Interrupted tone
1000
18 Interrupted tone
2500
19 Interrupted tone
2500
20 Interrupted tone
700
21 Interrupted tone
1000
22 Interrupted tone
700
23 Interrupted tone
700
24 Interrupted tone
720
25 Int,fast,rising volume
1400
26 Fast siren
250-1200
27 Rising constant, fall
1000
28 ISO 8201 Evacuation
800-1000
29 Fast whoop
500-1000
30 Slow whoop
500-1200
31 Reverse sweep
1200-500
32 Siren
500-1200
MOUNTING: The Y05 series alarm units are mounted to a wall or bulkhead of suitable material using the lugs projecting from the
side of the case. The lugs are bored 8mm clearance on 153mm centres. The recommended length of fixing screws is 25mm. To
maintain the integrity of the weather seal, the cable entry must be via a suitable sealed gland.
rept.
Second
switches
rate
Stage
1 2 3 4 5
0.5
3
1 1 1 1 1
0.5
4
0 1 1 1 1
0.25
7
1 0 1 1 1
0.25
8
0 0 1 1 1
0.4/0.1
14
1 1 0 1 1
1.0
14
0 1 0 1 1
0.13
12
1 0 0 1 1
0.07
13
0 0 0 1 1
2.0
10
1 1 1 0 1
-
1
0 1 1 0 1
-
31
1 0 1 0 1
-
7
0 0 1 0 1
-
2
1 1 0 0 1
-
9
0 1 0 0 1
2.0
31
1 0 0 0 1
1.25
30
0 0 0 0 1
0.5
1
1 1 1 1 0
0.25
4
0 1 1 1 0
0.5
2
1 0 1 1 0
6/12
10
0 0 1 1 0
1.0
32
1 1 0 1 0
4.0
10
0 1 0 1 0
0.25
10
1 0 0 1 0
0.7/0.3
10
0 0 0 1 0
0.25
26
1 1 1 0 0
0.085
11
0 1 1 0 0
10/40/10
17
1 0 1 0 0
as std
11
0 0 1 0 0
0.15
32
1 1 0 0 0
4.5
12
0 1 0 0 0
1
11
1 0 0 0 0
3.0
26
0 0 0 0 0
switch settings: ON=1 and OFF=0
Special Application
Fire Alarms
Security Alarms
Increased urgency
Security deterrent
AFNOR, France
Turn-out, Sweden
All-clear, Sweden
AS2220, Australia
Pre-vital mess, Sweden
Air-raid, Sweden
Local warning, Sweden
Industrial alarm, Germany
Industrial alarm, Germany
Int'l evacuation alarm
Evacuation, The Netherlands
Evacuation, Germany
D7426/4

Advertisement

loading
Need help?

Need help?

Do you have a question about the Clifford & Snell Y05 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Stahl Clifford & Snell Y05

  • Page 1 Y05/YL5 INSTALLATION INSTRUCTIONS General Description: This application should be installed and used as recommended by the National Fire Protection Association standards and practices. The Installer should be familiar with these requirements together with any local codes or special requirements of the local Fire Authority having jurisdiction.
  • Page 2 2nd SOUNDER WIRING DETAILS FOR YL UNITS POLAR DIAGRAM OF TONE 11 (see Website for all tones) A GROUP OF R. STAHL, WALDENBURG, GERMANY R. STAHL (P) Ltd., R. STAHL (P) Ltd., R. STAHL (P) Ltd., R. STAHL (P) Ltd., Plot No: 5, Malrosapuram Main Road, Sengundram Industrial Area, Malrosapuram –...