User Guide | ERC 112 Refrigeration Controller
"Cdd"
Compressor Door Open Delay/Cdd
This parameter sets the delay in minutes before the compressor stops
Min. 0 min
when the door is opened. If set to zero, the function is disabled.
Max. 15 min
Default 0 min
"Srt"
System resume after door open
Fan and Compressor resume after cut out by door open.
Min. 0 min
Max. 60 min
Default 0 min
"Pod"
Power ON Delay
This is the delay in seconds between power-on and the compressor being
Min. 0 s
activated.
Max. 300 s
Default 300 s
Depends on the power ON temperature setting as explained below.
"Pot"
Power ON Temperature
This parameter is used to accelerate the first application test on the
Min. -100.0°C
OEM assembly line; if the cabinet temperature is higher than this
Max. 200.0°C
Default -100.0°C
parameter the power ON Delay is overruled and the outputs are activated
without delay.
Con
Condenser Protection settings
NOTE: A condensor temperature sensor is required to use these parameters.
Condenser protection is generally used in dusty environments where
the condenser may accumulate a layer of dust or dirt and therefore be
at risk of overheating.
"CAL"
Condenser Alarm Limit/CAL
This parameter sets the temperature for the condenser at which an alarm
Min. 0°C
will be generated.
Max. 200°C
Default 80°C
"CbL"
Condenser Block Limit/CbL
This parameter sets the temperature which if reached will cause the
Min. 0°C
compressor to switch OFF.
Max. 200°C
Default 85°C
"CoL"
Condenser OK Limit/CoL
This parameter sets the temperature at which the compressor is
Min. 0°C
allowed to start again after the temperature set in "CbL" above has been
Max. 200°C
exceeded and the compressor stopped.
Default 60°C
"CLL"
Condenser Low Limit/CLL
This parameter sets the lowest (condenser) temperature at which the
Min. -100°C
compressor is allowed to start.
Max. 20°C
Default -5°C
diS
Display settings
NOTE: some display parameters can be set in such as way that they
may be illegal in some jurisdictions. Please check local legislation.
"diC"
Display intensity auto control
"no": display intensity use fixed value.
Min. no
Max. yes
Default no
"din"
Display Intensity
The controller can have its display intensity (brightness) set in one of
Min. 2
two ways:
Max. 10
A) With a Danfoss ambient light sensor attached, the brightness of the
Default 10
display is adjusted automatically according to the ambient light level
(see the assignments section).
B) When no ambient light sensor is attached, the display intensity can
be set to a fixed intensity.
Both options are on a scale of 1 to 10, where 10 is the brightest.
© Danfoss | DCS (vt) | 2019.07
BC200686422115en-000802 | 15