Piping Insulation - Panasonic CS-XE9WKUAW Service Manual

Hide thumbs Also See for CS-XE9WKUAW:
Table of Contents

Advertisement

XE15****
1
Remove control board cover (Resin and
Metal).
2
Remove particular plate.
3
Remove plugs.
4
Fix the conduit connectors to the knockout
holes with lock-nuts, then secure them against
the side panel.
5
All wires pass through conduits & particular
plate's opening hole.
6
Connection wires between indoor unit and
outdoor unit should be UL listed or CSA
approved 4 conductor wires minimum AWG16
in accordance with local electric codes.
7
Wire connection to the power supply
(208/230V 60Hz) through circuit breaker.
Connect the UL listed or CSA approved
o
wires minimum AWG14 to the terminal
board, and connect the other end of the
wires to ELCB/ GFCI.
8
Connect the power supply cord and
connecting wire between indoor unit and
outdoor unit according to the diagram below.
9
Secure the wire onto the control board with
the holder (clamper).
This equipment must be properly earthed.
Earth lead wire shall be Yellow/Green (Y/G) in
colour and should be longer than other lead wires
as shown in the figure for electrical safety in case
of slipping.
11.3.5

Piping Insulation

1
Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E FOAM with thickness 1/4" (6 mm) or above.
Indoor Unit
T
r e
m
n i
l a
208/230V min AWG16
1
208/230V min AWG16
2
208/230V min AWG16
3
Grounding wire
min AWG16
WARNING
10 After completing wiring connections, reattach
the particular plate and control board cover
(metal and resin) to the original position with
the screws.
11 For wire stripping and connection
requirement, refer to instruction 11.2.3 of
indoor unit.
Front
Panel
Particular
Plate
Lock Nuts
Knockout
Holes
Outdoor Unit
T
r e
m
n i
l a
1
2
3
Disconnect Switch
Field supply
L1
L2
Grounding wire
Earth wire
longer
than other
AC wires
for safety
reasons
55
Connecting wires
Control Board
Cover (Metal)
Plugs
Connectors
Particular Plate
Opening hole
Power Supply
Single Phase
208/230V 60Hz
min AWG14
Indoor &
Power
outdoor
supply
connection
cord
cable
Control Board
Cover (Resin)
Terminal
Board
Earth wire
longer
than other
AC wires
for safety
reasons
Holder