During above condition, when indoor heat exchanger temperature is below 41°F (5°C), the outdoor fan will stop
according to outdoor piping temperature as following:

13.4 Airflow Direction

There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by
vertical vanes).
Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using
remote control).
13.4.1

Vertical Airflow

13.4.1.1
CS-XE9WKUAW CS-XE12WKUAW CS-XE15WKUAW
Operation Mode
Auto with Heat
Heating
Temperature
Cooling and Fan
Soft Dry
1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the
angles as stated above. For heating mode operation, the angle of the vane depends on the indoor heat
exchanger temperature as Figure 1 below. It does not swing during fan motor stop. When the air conditioner is
stopped using remote control, the vane will shift to close position.
2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and
the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the
vane will shift to close position.
136.4°F (58°C)
B
96.8°F (36°C)
Indoor Heat
Exchanger Temperature
OD Pipe Temp.
Airflow Direction
A
Exchanger
B
C
Manual
Auto
Manual
Auto
Manual
C
122.0°F (50°C)
86.0°F (30°C)
A
Figure 1
OD Pipe Temperature
A
78.8°F (26°C)
B
91.4°F (33°C)
Outdoor
fan ON
86°F (30°C)
Outdoor
fan OFF
Upper Vane Angle (°)
1
2
3
67
95
67
67
83
88
65 ~ 115
65
67
94
65 ~ 115
65
67
94
Closed Position
Reference point
Step 1
Step 2
68
Lower Vane Angle (°)
4
5
1
2
95
110
63
75
100
115
58
63
100
115
58
63
Step 3
Step 4
Step 5
Figure 2
3
4
5
63
92
63
85
92
105
58 ~ 100
70
80
100
58 ~ 100
70
80
100
Upper vane: 60°
Lower vane: 58°