This equipment must be properly earthed.
Front Panel
Particular
Lock Nuts
Knockout
Holes
12.3.5
Piping Insulation
1
Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E FOAM with thickness 1/4" (6 mm) or above.
12.3.5.1
Cutting and flaring the piping
1
Please cut using pipe cutter and then remove the burrs.
2
Remove the burrs by using reamer. If burrs are not removed, gas leakage may be caused. Turn the piping
end down to avoid the metal powder entering the pipe.
3
Please make flare after inserting the flare nut onto the copper pipes.
1. To cut
12.3.6
Disposal of Outdoor Unit Drain Water
The unit should be mounted on a stand that suits to a local environmental requirement.
When the Drain elbow being used, please ensure to:-
Provide a minimum clearance of 2" (50mm) to access the bottom of base pan.
o
Seal the four 25/32" (20mm) diameter holes with Rubber caps (refer to illustration below).
o
Use a rigid or flexible PVC pipe (local supply) to dispose drained water from the elbow or use a stainless
o
steel tray (local supplied) to collect and dispose water.
If the unit is used in an area where temperature falls below 32°F (0°C) for 2 or 3 consecutive days, it is
recommended not to use the Drain elbow and Rubber caps, water from defrost process will trap, freeze up and
obstruct fan rotation. Water may drip from the basepan hole area during defrost function, do not stand or place
objects underneath.
WARNING
Connecting wires
Control Board
Cover (Metal)
Plate
Plugs
Connectors
Particular
Plate's
Opening hole
Pipe
Reamer
Bar
Point d own
Clamp handle
3. To flare
2. To remove burrs
Rubber cap
Earth lead wire shall be Yellow/Green (Y/G) in
colour and should be longer than other lead wires
as shown in the figure for electrical safety in case
of slipping.
Terminal
Board
Control Board
Cover (Resin)
Earth wire
longer
than other
AC wires
for safety
reasons
Holder
Handle
1
0 –
/
32
Bar
Yoke
Core
Copper
Red arr o w mark
pipe
x 4
64
Terminal
Board
Earth wire
longer
than other
AC wires
for safety
reasons
Holder
Indoor &
Power
outdoor
supply
connection
cord
cable
■Improper flaring■
" (0-0.5 mm)
Inclined Surface
Cracked Uneven
damaged
thickness
When properly flared, the internal surface of the
flare will evenly shine and be of even thickness.
Since the flare part comes into contact with the
connections, carefully check the flare finish.
Drain
elbow