Partial Discharge

Parameter
Period to calculate PD trend
High noise level high
PD max level warning
PD max level alarm
PD average level warning
PD average level alarm
PD average level trend warning
1
Alarm limits and settings must be revised a few weeks after installation by customer depending
on bushing behaviour.
2
Value of zero disables this particular alarm.
Figure 14: Alarm > Partial Discharge tab
Suggested Value or Source of Data
Default
24 h
0 (disabled)
8000 pC
12000 pC
1000 pC
2000 pC
0 (disabled)
BMT330UM
v1.0
1
Allowable range
0 to 720
0 to 100
0 to 65000
0 to 65000
0 to 65000
0 to 65000
0 to 65000
20-Jun-16