Connection Terminals - Siemens Synco 200 SEZ220 Documentation On Basics

Signal converter
Table of Contents

Advertisement

Key
36 / 46
Siemens
Building Technologies
10.2

Connection terminals

G
X1 M
X2 M G1
G0
G1
Y1
G0
G, G0
Rated voltage AC 24 V.
G1
Power supply AC 24 V for active sensors or signal sources.
M
Measuring neutral for signal input.
G0
System ground for signal output.
X1...X5
Universal signal inputs (analog signals only)
for LG-Ni 1000, 2x LG-Ni 1000, T1, Pt 1000, DC 0...10 V, 0...1000 Ω.
Y1, Y2
Measured value or control outputs, analog DC 0...10 V.
SEZ220 signal converter
Electrical connections
X3 M
X4 M G1
X5 M
G1
Y2 G0