9 Trouble Shooting

In most situations, the inverter requires very little service. However, if inverter is not able to work perfectly,
we recommend the following solutions for quick troubleshooting.
Error display
Possible causes
GFCI Device Fault
Leakage current sensor fault
1.AC side incorrect wiring
Bus High Fault
2、Machine failure
1.AC side incorrect wiring
2、 Trip, switching capacity on
No Utility
grid-side is too small3 、
Electricity grid abnormal
4、Machine failure
Ground
Current
1.PV(+) or PV(-) earthing
Fault
2.Machine failure
AC side incorrect wiring
Bus Fault
Machine failure
1.AC side incorrect wiring
Over Current
2、Electricity grid abnormal
3、Machine failure
1.The machine is exposed to
sun.
Over Temperature
2.the ambient temperature is
Fault
too high
3、Machine failure
1.Start-up voltage of panels
PV Over Fault
is too high
2、Machine failure
1.AC side incorrect wiring
M Grid Volt Fault
2、Electricity grid abnormal
3、Machine failure
Corresponding measures
Please contact with local dealer if error remains the same after
several reset.
1.Disconnect the input/output switch, check the AC-side wiring
and reseat the plug to rule out bad contact.
2、Please contact with local dealer if error remains the same
after several reset.
1.Disconnect the input/output switch, check the AC-side wiring
and reseat the plug to rule out bad contact.
2、Replace switch;
3 、 After electricity grid returns to normal, the machine will
automatically restart;
4、Please contact with local dealer if error remains the same
after several reset.
1.Check PV(+) and PV(-) ground impedance , make
sure impedance is more than 2MΩ;
2.Please contact with local dealer if error remains the same
after several reset.
1.Disconnect the input/output switch, check the AC-side wiring
and reseat the plug to rule out bad contact.
2、Please contact with local dealer if error remains the same
after several reset.
1.Disconnect the input/output switch, check the AC-side wiring
and reseat the plug to rule out bad contact.
2 、 After electricity grid returns to normal, the machine will
automatically restart;
3、Please contact with local dealer if error remains the same
after several reset.
1. Lower machine surrounding temperature or move it to a
lower temperature place.
2、Please contact with local dealer if error remains the same
after several reset.
1.Adjustthepanel configuration to lower the input voltage.
2、Please contact with local dealer if error remains the same
after several reset.
1.Disconnect the input/output switch, check the AC-side wiring
and reseat the plug to rule out bad contact.
2 、 After electricity grid returns to normal, the machine will
28