EPO (Emergency Power Off)
The EPO port is located at the rear of the UPS panel. This circuit is normally closed
by a jumper connected to it supplied with the UPS. If this connector is opened, the
UPS will stop the output and enter a fault mode with 'EPO active' alarm. To recover
to normal operating state, below steps should be taken:
Reconnect EPO connector
Clear the EPO alarm by selecting 'reset fault state in the LCD screen. The UPS
will go to bypass mode.
Press and hold the on/off button until the UPS output restarts.
Dry Contacts (input/output)
The dry input contact is an optical coupling input interface, and is to be connected
to an external switch. The functions are programmable from the LCD screen. This
allows for remote operations such as powering on/off of the UPS.
The dry output contact is a normally open relay interface. This is used to indicate
the various status of the UPS that is programmable from the LCD screen.
Reference 7.3.4 to setting Dry in & out details