5. Modules using Konect PakBus
Router (private dynamic IP)
5.1 Set up hardware
1. Connect the Cellular antenna.
2. Connect your data logger to the CELL200-series
module RS-232 or CS I/O port.
3. If not connecting through CS I/O, provide power to the
CELL200 series.
5.2 Configure data logger
1. Connect to your data logger by using Device
Configuration Utility.
2. On the Network Services tab in the PakBus/TCP Client
field, enter the DNS address and Port number noted
during the Konect PakBus Router setup.
3. On the PPP tab, set Config/Port Used to CS I/O SDC8 or
RS-232, depending on how you are connected to the
data logger.
4. (Optional) On the PPP tab, set User Name and Password
if required by your cellular carrier (usually outside of
the United Sates).
5. Verify the Modem Dial String setting is blank.
6. If connecting through RS-232, on the Comport Settings
tab, set RS232 BaudRate to 115200 Fixed.
7. Shut down Device Configuration Utility and start it
again. This will activate the Cellular tab needed for the
next step.
8. On the Cellular tab, enter the APN provided by your
cellular provider.
9. On the Datalogger tab enter the PakBus/TCP Password
twice. This setting specifies a password that will make
the data logger authenticate any incoming or outgoing
PakBus/TCP connection. It must match the value entered
in the Konect PakBus Router setup.
10. Click Apply to save the changes.
3