5.3 Set up LoggerNet
1. Select Add Root > IPPort.
2. Select PakBusPort and pbRouter for PakBus data
loggers such as the CR1000X or CR300.
3. Add a data logger to the pbRouter.
4. Select the IPPort in the Network Map. Enter the Konect
PakBus Router DNS address and port number as noted
in the Konect PakBus Router setup. The DNS address
and port number are input in the Internet IP Address
field separated by a colon. For example,
axanar.konectgds.com:pppp where pppp is the port
number.
5. For PakBus data loggers, leave the default settings for
the PakBusPort. PakBus Port Always Open should not be
checked. Enter the TCP Password; this must match the
value entered in the Konect PakBus Router setup and
LoggerNet setup.
6. For PakBus data loggers, select the pbRouter in the
Network Map and set the PakBus Address to 4070.
7. For PakBus data loggers, select the data logger in the
Network Map and set the PakBus Address to match that
of the data logger (default address in the data logger is
1). If a PakBus Encryption Key was entered during data
logger setup, also enter it here. Click Apply to save the
changes.
5.4 Test the connection
Use the Connect screen to test the connection. Click on the
appropriate station and click Connect to initiate a call to the
data logger.
TIP:
The connection time is subject to many external factors. It
is often less than 30 seconds but could be up to fifteen
minutes. Be patient.
If the call is successful, the connectors at the bottom of the
screen will come together and clock information from the data
logger will be displayed in the Station Date/Time field.
4