Vertiv Liebert DPM User Manual page 78

Table of Contents

Advertisement

Table 10.6 Common Events
Component
Subcomponent
Board Name
Board Name
Board Name
[BAM #]
Board Name
Board Name
Board Name
Component
Name
Component
Name
Component
Name
74
Type
Event Name
ID
Latching
System
Status
2
Shutdown EPO
System Reset
Status
11
By User
Communication
Fault
12
Fail
Comms
13
Misconfiguration
No Initial
14
Comms
System Clock
Status
15
Set
Peak Current
Status
16
Reset
Peak Demand
Status
17
Reset
Status
kWH Reset
18
Definition
An EPO has been pressed record the event and trip the input breaker.
N
EPO Source: 1 = Local EPO 2 = Remote EPO NO 3 = Remote EPO
NC. The input breaker(s) will be tripped as a result of this event.
N
The monitor board received a command to reset latched events
Communication has been lost to this board (HMI or Peripheral board
for DSPs) for 20 seconds. The HMI detects comm fails to the
N
monitoring boards and sends an event to each respective board once
comms are restored.
N
Use by HMI. No logging.
N
The time or date has been set by the user (not time sync) or a time
N
source change (i.e., NTP. Unity card). HMI detects sends event record
to all Power Monitoring boards for logging.
Recorded at every monitor board. A command was received at the
monitor board to clear Peak Current value(s). Panel and breaker
number are 1' s based like config. A scope of Global reset will be
represented as parametric data: Panel A/B: 1 = Panel A, 2 = Panel B
N
Branch N0.: 0 = Mains, 1 to 84 = Branch No., 0xFF = Mains and
Branch on this panel. Parametric Data Examples: XFM: 0, 0, 0 PBM: 1
or 2 (panel), 0xff (All branches), 0 PBM: 1 or 2 (panel), 0 to 84
(branch), 0 SFM, I-Line: 0, 0xff (All subfeeds), 0 SFM, I-Line: 0, 0 to 12
(branch), 0 SFM: 0, 1 to 12 (subfeed), 0.
Recorded at every monitor board. A command was received at the
monitor board to clear Peak Current value(s). Panel and breaker
number are 1' s based like config. A scope of Global reset will be
represented as parametric data: Panel A/B: 1 = Panel A, 2 = Panel B
N
Branch N0.: 0 = Mains, 1 to 84 = Branch No., 0xFF = Mains and
Branch on this panel. Parametric Data Examples: XFM: 0, 0, 0 PBM: 1
or 2 (panel), 0xff (All branchs), 0 PBM: 1 or 2 (panel), 0 to 84 (branch),
0 SFM, I-Line: 0, 0xff (All subfeeds), 0 SFM, I-Line: 0, 0 to 12 (branch),
0 SFM: 0, 1 to 12 (subfeed), 0.
Recorded at every monitor board. A command was received at the
monitor board to clear Peak Current value(s). Panel and breaker
number are 1' s based like config. A scope of Global reset will be
represented as parametric data: Panel A/B: 1 = Panel A, 2 = Panel B
N
Branch N0.: 0 = Mains, 1 to 84 = Branch No., 0xFF = Mains and
Branch on this panel. Parametric Data Examples: XFM: 0, 0, 0 PBM: 1
or 2 (panel), 0xff (All branchs), 0 PBM: 1 or 2 (panel), 0 to 84 (branch),
0 SFM, I-Line: 0, 0xff (All subfeeds), 0 SFM, I-Line: 0, 0 to 12 (branch),
0 SFM: 0, 1 to 12 (subfeed), 0.