Table 10.3 SFM User Events (continued)
Component
Subcomponent
SFM Panel
Name
SFM Panel
Name
SFM Panel
Name
SFM Panel
Name
SFM Panel
Name
SFM Panel
Subfeed # Label
Name
SFM Panel
Subfeed # Label
Name
SFM Panel
Subfeed # Label
Name
SFM Panel
Subfeed # Label
Name
SFM Panel
Subfeed # Label
Name
SFM Panel
Subfeed # Label
Name
SFM Panel
Subfeed # Label
Name
SFM Panel
Subfeed # Label
Name
SFM Panel
Subfeed # Label
Name
72
Type
Event Name
ID
Latching
Energy
Status
Measure
308
N
Rollover
Main Breaker
Status
309
N
Open
Main Breaker
Status
310
N
Closed
Main Breaker
Fault
311
N
Tripped
Main Breaker
Fault
312
N
Acc Error
Phase
Fault
332
L
Overcurrent
Phase
Alarm
333
L
Overcurrent
Neutral
Fault
334
L
Overcurrent
Ground
Fault
335
L
Overcurrent
Energy
Status
Measure
336
N
Rollover
Breaker
Status
337
N
Open
Breaker
Status
338
N
Closed
Breaker
Fault
339
N
Tripped
Breaker
Fault
Accessory
340
N
Error
Definition
The kWH Total measurement has exceeded it max value.
The Subfeed Main Breaker Aux lines are report open.
The Subfeed Main Breaker Aux lines are report closed.
The Subfeed Main Breaker Bell sensing has changed state (normal to
tripped).
The Subfeed Main Breaker sensing is an erroneous state. Parametric
data logged with this event will indicate the nature of the first cause. Error
Type: 1 = Form C position (Aux) sensing is not complementary. 2 = Form
C trip (Bell) sensing is not complementary. 3 = Trip (Bell) sensing is
indicating a tripped breaker but the position (Aux) sensing is indicating a
closed breaker.
One of the I rms phases has exceeded the alarm setpoint for the set
period.
One of the I rms phases has exceeded the warning setpoint for the set
period.
The In rms has exceeded the alarm setpoint for the set period.
The Ig rms has exceeded the alarm setpoint for the set period.
The kWH Total measurement has exceeded its maximum value.
Parametric data 2 indicates Subfeed number (1-12).
The Subfeed Breaker Aux lines are reported open.
The Subfeed Breaker Aux lines are reported closed.
The Subfeed Breaker Bell sensing has changed state (normal to tripped).
The Subfeed Breaker sensing is an erroneous state. Parametric data
logged with this event will indicate the nature of the first cause. Error
Type: 1 = Form C position (Aux) sensing is not complementary. 2 = Form
C trip (Bell) sensing is not complementary. 3 = Trip (Bell) sensing is
indicating a tripped breaker, but the position (Aux) sensing is indicating a
closed breaker.