Table 10.2 PBM Events (continued)
Component
Subcomponent
PBM Mains
Label
PBM Mains
Label
PBM Mains
Label
PBM Mains
Label
PBM Mains
Breaker # Label
Label
PBM Mains
Breaker # Label
Label
PBM Mains
Breaker # Label
Label
PBM Mains
Breaker # Label
Label
Table 10.3 SFM User Events
Component
Subcomponent
SFM Panel
Name
SFM Panel
Name
SFM Panel
Name
SFM Panel
Name
SFM Panel
Name
SFM Panel
Name
SFM Panel
Name
SFM Panel
Name
10 Faults, Warnings and Events
Type
Event Name
ID
Definition
Main
Status
Breaker
209
The Panel Main Breaker Aux lines are reported open.
Open
Main
Status
Breaker
210
The Panel Main Breaker Aux lines are reported closed.
Closed
Main
Fault
Breaker
211
The Panel Main Breaker Bell sensing has changed state (normal to tripped).
Tripped
The Panel Main Breaker sensing is an erroneous state. Parametric data logged with
Main
this event will indicate the nature of the first cause. Error Type: 1 = Form C position
Fault
Breaker Acc
212
(Aux) sensing is not complementary. 2 = Form C trip (Bell) sensing is not
Error
complementary. 3 = Trip (Bell) sensing is indicating a tripped breaker but the position
(Aux) sensing is indicating a closed breaker.
Fault
Overcurrent
232
One of the breaker I rms phases has exceeded the alarm setpoint for the set period.
Alarm
Overcurrent
233
One of the I rms phases has exceeded the warning setpoint for the set period.
Fault
Undercurrent
234
All of the I rms phases are below the setpoint for the set period.
Energy
The kWH Total measurement has exceeded its maximum value. Parametric data 1
Status
Measure
235
indicates panel. Parametric data 2 indicates breaker (1-84).
Rollover
Type
Event Name
ID
Latching
Fault
Overvoltage
300
L
Fault
Undervoltage
301
L
Phase
Fault
302
L
Overcurrent
Phase
Alarm
303
L
Overcurrent
Neutral
Fault
304
L
Overcurrent
Ground
Fault
305
L
Overcurrent
Frequency
Fault
306
L
Deviation
Summary
Alarm
307
N
Alarm
Definition
One of the VLL rms phases has exceeded the setpoint for the set period.
One of the VLL rms phases is below the setpoint for the set period.
One of the I rms phases has exceeded the alarm setpoint for the set
period.
One of the I rms phases has exceeded the warning setpoint for the set
period.
The In rms has exceeded the alarm setpoint for the set period.
The Ig rms has exceeded the alarm setpoint for the set period.
The measured frequency has fallen outside the range specified in the
frequency setpoint
The occurrence of any subfeed or subfeed main alarm (activeLatched).
71