Table 10.1 XFM User Events (continued)
Component
Type
Input 2
Fault
Input 2
Fault
Input 1
Fault
Input 1
Fault
Input 1
Fault
Input 2
Fault
Input 2
Fault
Input 2
Fault
Input 2
Fault
Input 2
Fault
Input 2
Fault
Table 10.2 PBM Events
Component
Subcomponent
PBM Mains
Overvoltage
Label
PBM Mains
Undervoltage
Label
PBM Mains
Label
PBM Mains
Label
PBM Mains
Label
PBM Mains
Label
PBM Mains
Label
PBM Mains
Label
PBM Mains
Label
70
Event Name
ID
Definition
The Main Input Breaker 2 sensing is an erroneous state. Parametric data logged with this event will
Breaker Acc
indicate the nature of the first cause. Error Type: 1 = Form C position sensing (Aux) is not
124
Error
complimentary. 2 = Form C trip sensing (Bell) is not complementary. 3 = Trip (Bell) sensing is
indicating a tripped breaker but the position sensing (Aux) is indicating a closed breaker.
Breaker Open
125
The breaker was commanded to open but sensing did not show open within a 2 second period
Fail
Undervoltage
127
One of the VLL rms phases is below the setpoint for the set period.
Overvoltage
128
One of the VLL rms phases has exceeded the setpoint for the set period.
Frequency
129
The measured frequency has fallen outside the range specified in the frequency setpoint
Deviation
Undervoltage
130
One of the VLL rms phases is below the setpoint for the set period.
Overvoltage
131
One of the VLL rms phases has exceeded the setpoint for the set period.
Frequency
132
The measured frequency has fallen outside the range specified in the frequency setpoint.
Deviation
Invalid Phase
133
The input phases are not in the normal A-B-C sequence.
Rotation
Phase Loss
134
The input phase voltages are unbalance by 20% and all voltages are greater than 50v.
High Voltage
135
One of the voltage THD readings has exceeded the alarm setpoint .
THD
Type
Event Name
ID
Fault
Overvolt
200
Fault
Undervolt
201
Phase
Fault
202
Overcurrent
Phase
Alarm
203
Overcurrent
Neutral
Fault
204 The In rms has exceeded the alarm setpoint for the set period.
Overcurrent
Ground
Fault
205
Overcurrent
Frequency
Fault
206
Deviation
Panel
Alarm
207
Summary
Energy
Status
Measure
208
Rollover
Definition
One of the VLL rms phases has exceeded the setpoint for the set period.
One of the VLL rms phases is below the setpoint for the set period.
One of the I rms phases has exceeded the alarm setpoint for the set period.
One of the I rms phases has exceeded the warning setpoint for the set period.
The Ig rms has exceeded the alarm setpoint for the set period.
The measured frequency has fallen outside the range specified in the frequency
setpoint
The occurrence of any branch or panelboard main alarm (activeLatched).
The kWH Total measurement has exceeded its max value. Parametric data 1
indicates panel.