Control characteristics:
Frequency range .................................................................................................................................. 0 - 1000 Hz
Resolution on output frequency ............................................................................................................. ±0.003 Hz
System response time ............................................................................................................................... 3 msec.
Speed, control range (open loop) ..................................................................................... 1:100 of synchro. speed
Speed, control range (closed loop) ................................................................................. 1:1000 of synchro. speed
Speed, accuracy (open loop) .............................................................................. < 1500 rpm:max. error ± 7.5 rpm
> 1500 rpm: max. error of 0.5% of actual speed
Process, accuracy (closed loop) ......................................................................... < 1500 rpm: max.error ± 1.5 rpm
> 1500 rpm: max. error of 0.1% of actual speed
All control characteristics are based on a 4-pole asynchronous motor
Accuracy of display readout (parameters 009-012 Display readout):
Motor current, 0 - 140% load ................................................................. Max. error: ±2.0% of rated output current
Power kW, Power HP, 0 - 90% load ........................................................ Max. error: ±5.0% of rated output power
Externals:
Enclosure .................................................................................................................... Chassis, NEMA 1, NEMA 12
Vibration test .................................. 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)
Max. relative humidity ............................................................. 93 % +2 %, -3 % (IEC 68-2-3) for storage/transport
Max. relative humidity ................................................ 95% non condensing (IEC 721-3-3; class 3K3) for operation
Ambient temperature Chassis/NEMA 1/NEMA 12 ................................... Max. 45°C (24-hour average max. 40°C)
Ambient temperature NEMA 1/NEMA 12 VLT 4011 460 V ..................... Max. 40°C (24-hour average max. 35°C)
see Derating for high ambient temperature
Min. ambient temperature in full operation ........................................................................................................ 0°C
Min. ambient temperature at reduced performance ..................................................................................... -10°C
Temperature during storage/transport ............................................................................................. -25 - +65/70°C
Max. altitude above sea level ................................................................................................................... 3300 feet
see Derating for high air pressure
VLT 4000 VTprotection:
Electronic motor thermal protection against overload.
Temperature monitoring of heat-sink ensures that the VLT AFD cuts out if the temperature reaches 90°C
for Chassis and NEMA 1. For NEMA 12, the cut-out temperature is 80°C. An overtemperature can only
be reset when the temperature of the heat-sink has fallen below 60°C. VLT 4152-4202, 380-460 V
cuts out at 80°C and can be reset if the temperature has fallen below 60°C. VLT 4252-4352, 380-460
V cuts out at 105°C and can be reset if the temperature has fallen below 70°C.
The VLT AFD is protected against short-circuiting on motor terminals U, V, W.
The VLT AFD is protected against ground fault on motor terminals U, V, W.
Monitoring of the intermediate circuit voltage ensures that the VLT AFD cuts out if the
intermediate circuit volt-age gets too high or too low.
If a motor phase is missing, the VLT AFD cuts out.
If there is a line fault, the VLT AFD is able to carry out a controlled deramping.
If a line phase is missing, the VLT AFD will cut out when a load is placed on the motor.
16
VLT® 4000 VT
MG.40.A4.22 - VLT is a registered Danfoss trademark