Danfoss VLT 4000 ME Manual page 12

Advertisement

■ Line Supply, 3 x 525 - 600 V
Output
Output Current
Output
Typical shaft output
Typical shaft output
Max. copper cable
cross-section to motor
and loadsharing
2)
/AWG]
Min. cable cross-section
to motor
and loadsharing
2)
/AWG]
Input
Rated Input Current
Max. copper cable
cross-section power,
4)
NEMA 1
[mm
Max. pre-fuses (mains)
Efficiency
Weight IP20 / NEMA 1
Estimated power loss at
max. load
Enclosure
1. See section Fuses.
2. American Wire Gauge (AWG).
3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted into the terminals to comply with IP 20. Always comply with national and
local regulations on min. cable cross-section.
4. Aluminum cables with cross section above 35 mm
24
VLT type
I
[A] (550 V)
VLT,N
I
(60 s) [A] (550 V)
VLT, MAX
I
[A] (575 V)
VLT, N
I
(60 s) [A] (575 V)
VLT, MAX
S
[kVA] (550 V)
VLT,N
S
[kVA] (575 V)
VLT,N
P
[kW]
VLT,N
P
[HP]
VLT,N
4)
2
[mm
3)
2
[mm
I
[A] (550 V)
VLT,N
I
[A] (600 V)
VLT, N
2
2)
/AWG]
1)
1)
[-]/UL
[kg]
[lbs]
2
/AWG 2 must be connected by use of an Al-Cu connector.
VLT® 4000 VT
4 4 016
4022
4027
4032
18
23
28
34
20
25
31
37
17
22
27
32
19
24
30
35
17
22
27
32
17
22
27
32
11
15
18.5
22
15
20
25
30
16
16
16
35
6
6
6
2
0.5
0.5
0.5
10
20
20
20
8
18
22
27
33
16
21
25
30
16
16
16
35
6
6
6
2
[A]
20
30
35
45
23
23
23
30
51
51
51
66
[W]
451
576
707
852
MG.40.A4.22 - VLT is a registered Danfoss trademark
4042
4052
4062
4072
43
54
65
81
47
59
72
89
41
52
62
77
45
57
68
85
41
51
62
77
41
52
62
77
30
37
45
55
40
50
60
75
35
50
50
50
2
1/0
1/0
1/0
10
16
16
16
8
6
6
6
42
53
63
79
38
49
58
72
35
50
50
50
2
1/0
1/0
1/0
60
75
90
100
0.96
30
48
48
48
66
106
106
106
1077
1362
1628
2029
NEMA 1