■ Fuses
UL compliance
To comply with UL/cUL approvals, pre-fuses according to the table below must be used.
200-240 V
VLT
Bussmann
4006
KTN-R30
4008
KTN-R50
4011, 4016
KTN-R60
4022
KTN-R80
4027, 4032
KTN-R125
4042
FWX-150
4052
FWX-200
4062
FWX-250
380-460 V
Bussmann
4006
KTS-R20
4008
KTS-R25
4011
KTS-R30
4016, 4022
KTS-R40
4027
KTS-R50
4032
KTS-R60
4042
KTS-R80
4052
KTS-R100
4062
KTS-R125
4072
KTS-R150
4102
FWH-220
4122
FWH-250
4152
FWH-300
4202
FWH-350
4252
FWH-400
4302
FWH-500
4352
FWH-600
4450
FWH-700
4500
FWH-800
4600
FWH-800
26
VLT® 4000 VT
SIBA
Littel fuse
5017906-032
KLN-R30
5012406-050
KLN-R50
5014006-063
KLN-R60
5014006-080
KLN-R80
2028220-125
KLN-R125
2028220-150
L25S-150
2028220-200
L25S-200
2028220-250
L25S-250
SIBA
Littel fuse
5017906-020
KLS-R20
5017906-025
KLS-R25
5012406-032
KLS-R30
5014006-040
KLS-R40
5014006-050
KLS-R50
5014006-063
KLS-R60
2028220-100
KLS-R80
2028220-125
KLS-R100
2028220-125
KLS-R125
2028220-160
KLS-R150
2028220-200
L50S-225
2028220-250
L50S-250
2028220-315
L50S-300
2028220-315
L50S-350
206xx32-400
L50S-400
206xx32-500
L50S-500
206xx32-600
L50S-600
206xx32-700
L50S-700
206xx32-800
L50S-800
206xx32-800
L50S-800
MG.40.A4.22 - VLT is a registered Danfoss trademark
Ferraz-Shawmut
ATM-R30 or A2K-30R
A2K-50R
A2K-60R
A2K-80R
A2K-125R
A25X-150
A25X-200
A25X-250
Ferraz-Shawmut
ATM-R20 or A6K-20R
ATM-R25 or A6K-25R
ATM-R30 or A6K-30R
A6K-40R
A6K-50R
A6K-60R
A6K-80R
A6K-100R
A6K-125R
A6K-150R
A50-P225
A50-P250
A50-P300
A50-P350
A50-P400
A50-P500
A50-P600
A50-P700
A50-P800
A50-P800
Need help?
Do you have a question about the VLT 4000 ME and is the answer not in the manual?
Questions and answers