Device Installation

The SICAM FPI device is intended for indoor installation in an RMU panel.
Execute the following procedure to install and mount the device in RMU:
Create a slot of dimensions measuring 92+0.8 mm x 45+0.8 mm (W x H) to house the device in RMU
²
panel.
[dw_sicam-fpi_pnlcut, 1, en_US]
Figure 2-8
Flush the rear side of device into the cut-out.
²
20
6MD2310-0DX00-0AA0 - 3 Phase, 1 Ground, 1 Binary Output with 3 Phase Sensors and 1
Ground Sensor
6MD2310-0EX00-0AA0 - 1 Ground, 2 Binary Outputs with 1 Ground Sensor
RMU Panel Cut-Out
SICAM, Fault Passage Indicator, Manual
E50417-H1040-C580-A7, Edition 11.2019