Initial Settings - Panasonic PAW-160MAH2L Installation Instructions Manual

Air handling unit kit for panasonic ecoi; panasonic eco g; panasonic paci
Table of Contents

Advertisement

3. Confi rm the new setting by pressing the
The PV display now shows "nun", while the SV display now shows "3".
4. Press the
5. Use the
(= factory setting) for „output 0 ... 10V".
6. Confi rm the complete parametrization by pressing and holding the
matedly 3 seconds.
Parametrization is now complete. The PV and SV displays have returned to showing the cur-

rent temperature and the set temperature values respectively.

7.2.3 Initial Settings

Depending on how the thermostat is used in each individual application, its settings must be
adjusted for the relevant case.
Case 1: Controlling the room supply air temperature
To set the thermostat for controlling the room supply air temperature, perform the following
steps:
1. Open the AHU Kit enclosure (see "4.1 Installation of AHU Kit" – step 2).
2. On the thermostat, switch to PID mode by entering the "Parameter" menu and set parame-
ters P, I and D to the values given below (see "7.2.2 Operation – Changing values in the
'Parameter' menu").
AHU situation
(a) Capacity high and air volume fl ow low
(b) Capacity low and air volume fl ow high
These PID settings are intended to respond to AHU situations, where either the required
capacity is rather high (close to the upper limit of the nominal AHU kit capacity) while at the
same time the air volume fl ow is rather low (a), or vice versa (b).
If the initial PID setting results in an unstable temperature during operation, these values
may be adjusted manually at a later stage.
3. On the thermostat, switch to cooling or heating mode, depending on the AHU requirements
(for AHU Kit models equipped with thermostat TR-16, see "7.2.2 Operation – Switching from
'heating mode' to 'cooling mode'"; for models with TR-16e, this procedure is not required).
1 x briefl y
button repeatedly to select the entry "AO".
repeatedly
and
buttons to change the value to either "1" for "output 2 ... 10V" or "2"
1 x for 3 sec.
button.
Control
button for approxi-
P
I
D
7
120
3
3
180
10
91