Installation
● The thermistor wire must be inserted drooped in the AHU body with the drooping
wire being close to the AHU Kit.
i
Important
If there are multiple heat exchangers in one ECOi system, an individual thermistor must be
installed for each heat exchanger.

4.4.1 Installation of thermistor on gas pipe

Installation of thermistor on gas pipe – ECOi and ECO G systems
Mount "E3" thermistor to the gas pipe of the AHU heat exchanger according to the following
instructions.
For PAW-160MAH2(L/M)
1. Attach the gas pipe thermistor onto the collecting gas pipe in the heat exchanger.
2. Cover the thermistor and pipe with aluminum tape.
3. Cover the aluminum tape with thermal insulation.
46