Panasonic PAW-160MAH2L Installation Instructions Manual page 21

Air handling unit kit for panasonic ecoi; panasonic eco g; panasonic paci
Table of Contents

Advertisement

Supply exhaust type with rotary heat exchanger
Connecting AHU systems via the AHU Kit to ECOi/ECO G or PACi outdoor
units
The following graphic shows an example for connecting a third-party air handling unit via the
Panasonic AHU Kit to Panasonic ECOi/ECO G or PACi outdoor units.
Air handling unit control by external 0–10 V signal
PACi or ECOi/ECO G outdoor unit
1 This schematic layout applies to the advanced and medium AHU Kit versions only, because they feature an in-built
CZ-CAPBC2 interface handling the 0–10 V control. This enables various control alternatives:
Capacity control through external BMS via 0–10 V signal (only supported by ECOi and PACi, but not
by ECO G outdoor units)
Capacity control through in-built supply air or ambient temperature sensor (only available with ad-
vanced version and only supported by ECOi and PACi, but not by ECO G outdoor units)
Temperature setpoint control
2 As the "light" version of the AHU Kit does not include an in-built CZ-CAPBC2 interface for handling the 0–10 V con-
trol, this schematic layout does not apply to the "light" AHU Kit version.
Ventilation theory and air handling units
External control
system
Air Handling Unit Kit
AL1
PV
ºC
OUT
SV
ºC
ATU
SET
Air Handling Unit
19