Panasonic PAW-160MAH2L Installation Instructions Manual page 2

Air handling unit kit for panasonic ecoi; panasonic eco g; panasonic paci
Table of Contents

Advertisement

AHU Kit connects PACi outdoor units to Air Handling Units system.
The Panasonic AHU Kits offer a wealth of connectivity possibilities so can
be easily integrated into many systems.
Application: Hotels, offi ces, server rooms or all large buildings where air
quality control such as humidity control and fresh air and is needed.
3 types of AHU Kit: Deluxe, Medium and Light.
Model Code
IP 65
0-10V demand
control*
PAW-280PAH2
Yes
Yes
PAW-280PAH2M
Yes
Yes
PAW-280PAH2L
Yes
No
* With CZ-CAPBC2.
System & regulations. System overview
1. AHU Kit equipment (Field supplied)
2. AHU Kit system controller (Field supplied)
3. AHU Kit controller box (with control PCB)
4. Thermistor for Gas pipe (E2)
5. Thermistor for Liquid pipe (E1)
6. Thermistor for Suction air
7. Inter-unit wiring
8. Outdoor unit
Optional parts: Following functions are available by using different control accessories:
CZ-RTC4 Timer remote controller.
· Operation-ON/OFF
· Mode select
· Temperature setting
* Fan operation signal can be taken from the PCB.
PAW-OCT, DC12 V outlet. OPTION terminal.
· Output signal= Cooling/Heating/Fan status
· Defrost
· Thermostat-ON
AHU PACi Elite
PAW-280PAH2
PAW-280PAH2+PAW-280PAH2
* For U-200PE2E8A and U-250PE2E8A.
AHU connection kit / System combination
Outdoor unit capacity
AHU
5,00kW
PAW-280PAH2
6,00kW
PAW-280PAH2
7,50kW
PAW-280PAH2
10,00kW
PAW-280PAH2
12,50kW
PAW-280PAH2
14,00kW
PAW-280PAH2
20,00kW
PAW-280PAH2
25,00kW
PAW-280PAH2
Outdoor unit
8,00 8,33 9,00 10,00 10,83 11,67 12,00 13,00 13,33 14,00 15,00 16,00 16,67 18,00 19,00 20,00 25,00 26,67 28,00 30,00 33,00 35,00 36,00 38,00 40,00 43,33 45,00 50,00 58,33 66,00 66,67 71,67 74,00 75,00 83,33 90,00
5,00kW
6,00kW
7,50kW
10,00kW
12,50kW
14,00kW
20,00kW
25,00kW
Standard range of air flow rate under standard conditions (air intake temperature in cooling mode from 18 to 32°C DB).
Outdoor temperature shift
compensation. Cold draft prevention
Yes
No
No
2
1
3
7
4
5
8
6
CZ-CAPBC2 Mini seri-para I/O unit (advanced version only).
· Easy integration in external AHU control systems and BMS
· Demand control: 40 to 115 % (5 % steps) of nominal current by 0–10 V
input signal*
· Target temperature setting by 0–10 V or 0–140 Ω input signal*
· Mode select or/and ON/OFF control
· Fan operation control
· Operation status output/ Alarm output
· Thermostat ON/OFF control
* Demand control by external BMS cannot be combined with the demand control or target temperature
setting accomplished by the thermostat. However, if simultaneous demand control and target temperature
setting is needed, this can only be achieved by using a second (optional) CZ-CAPBC2 interface.
Cooling capacity
Heating capacity
Nominal
Nominal
kW
kW
6,00 / 25,00
7,00 / 28,00
50,00
56,00
Air volume
Dimensions
Min / Max
H x W x D
m³/min
mm
8,00 / 13,00
404 x 425 x 78
9,00 / 16,00
404 x 425 x 78
12,00 / 25,00
404 x 425 x 78
14,00 / 33,00
404 x 425 x 78
19,00 / 35,00
404 x 425 x 78
19,00 / 35,00
404 x 425 x 78
28,00 / 66,00
404 x 425 x 78
38,00 / 74,00
404 x 425 x 78
AL1
PV
ºC
OUT
SV
ºC
ATU
5
SET
1
3
2
6
4
AHU Connection Kit
PCB, Power trans,
Thermistor x2
Terminal block
(Refrigerant: E1, E2)
CZ-T10 terminal / PAW-T10 PCB to connect to T10 connector.
· A Dry contact PCB has been developed to easily control the unit
· Input signal operation ON/OFF
· Remote control prohibition
· Output signal Operation ON status maximum 230 V 5 A (NO/NC)
· Output signal alarm status max. 230 V 5 A (NO/NC)
· Alarm output (by DC12V)
· Additional available contacts:
- External humidifier control (ON/OFF) 230 VAC 3 A
- External fan control (ON/OFF) 12V DC
- External filter status signal potential free
- External float switch signal potential free
- External leakage detection sensor or TH. OFF contact potential free
Dimensions
Piping length
H x W x D
Min / Max
mm
404 x 425 x 78
404 x 425 x 78
Piping length
Elevation difference (in/out)
Min / Max
Max
m
m
5 / 30
10
5 / 30
10
5 / 30
10
5 / 30
10
5 / 30
10
5 / 30
10
5 / 70
10
5 / 70
10
Air flow rate m³/min
Extended range of air flow rate under special conditions (air intake temperature in cooling mode from 18 to 30°C DB).
NEW — COMMERCIAL
1. Remote control CZ-RTC4
2. New plastic IP 65 Box
3. PAW-T10 PCB for Dry Contact
4. 0-10V demand control PCB
5. Intelligent thermostat for:
· Cold draft prevention
· Outdoor temperature shift compensation
6. Terminal base for sensors and power supply
Thermistor
Standard wired remote controller.
(Air: TA; 1 sensor)
(possible usage for external blow out temperature control)
Elevation difference (in/out)
Max
m
m
5 / 30*
10
5 / 30*
10
Piping connections
Liquid pipe
Gas pipe
Inch (mm)
Inch (mm)
1/4 (6,35)
1/2 (12,70)
3/8 (9,62)
5/8 (15,88)
3/8 (9,62)
5/8 (15,88)
3/8 (9,62)
5/8 (15,88)
3/8 (9,62)
5/8 (15,88)
3/8 (9,62)
5/8 (15,88)
3/8 (9,62)
1 (25,40)
1/2 (12,70)
1 (25,40)
259