Panasonic PAW-160MAH2L Installation Instructions Manual page 56

Air handling unit kit for panasonic ecoi; panasonic eco g; panasonic paci
Table of Contents

Advertisement

Installation
3. Press the Temperature "UP" button (▲) just once shortly, in order to scroll to parameter "11".
4. With the Timer "UP" and "DOWN" buttons (▲▼) modify the parameter value according to the
following table:
PACi outdoor unit model
Standard
R410A
U-60PEY2E5
U-71PEY2E5
U-100PEY1E5
U-100PEY1E8
U-125PEY1E5
U-125PEY1E8
U-140PEY1E5
U-140PEY1E8
5. Confi rm the new setting by pressing the "SET" button.
6. Only for
Press the Temperature "UP" button (▲) just once shortly, in order to scroll to parameter "2C".
With the Timer "UP" and "DOWN" buttons (▲▼) modify the parameter value from the factory
default "0002" to the new value "0006".
Confi rm the new setting by pressing the "SET" button.
7. Exit the setting mode by pressing the "Spanner" button.
54
R32
U-60PZ2E5
U-71PZ2E5
U-100PZ2E5
U-100PZ2E8
U-125PZ2E5
U-125PZ2E8
U-140PZ2E5
U-140PZ2E8
R32
models:
Elite
R410A
R32
U-36PE2E5A
U-36PZH2E5
U-50PE2E5
U-50PZH2E5
U-60PE2E5A
U-60PZH2E5
U-71PE1E5A
U-71PZH2E5
U-71PE1E8A
U-71PZH2E8
U-100PE1E5A
U-100PZH2E5
U-100PE1E8A
U-100PZH2E8
U-125PE1E5A
U-125PZH2E5
U-125PE1E8A
U-125PZH2E8
U-140PE1E5A
U-140PZH2E5
U-140PE1E8A
U-140PZH2E8
U-200PE2E8
U-200PZH2E8
U-250PE2E8
U-250PZH2E8
Setting for AHU Kit
parameter "11"
0005
0009
0011
0012
0015
0017
0018
0021
0023

Hide quick links: