Mounting methods

All "Easy Light" can be mounted either surface or recess
mounted in walls or suspended ceilings. For recess
mounted installations, special accessories are required
which can be found in the catalog and must be ordered
separately.

Suspended ceiling installation.

On the bottom of the base plastic of the Easy light
luminaire there are two H shaped cut outs. These are
used to install the A-3018 mounting springs.
1. With a sharp tool remove the appropriate plastic
pieces to fit the mounting springs. First place the edges
of the mounting spring to the respective holes and install
the one end of the coil to the support axis.
2. Install the other end of the coil to the other support
axis.
3. Bend the springs and place the luminaire to the
respective suspended ceiling's hole.
The luminaire's placement to the suspended ceiling
must be done after the connection with power supply
cables.

Recess mounting in a wall

The special mounting base (A-3016) can be built in the
wall and on it can be mounted the luminaire with the Α-
3016 included screws, following the installation
instructions of the luminaire. The mounting base
contains pre-etched holes for cable entry that are
aligned with the cable entry holes of the luminaire.
PLACING Α-CRV PARTS
To install the curve crystal Α-CRV you must first install the
included plastic extension to mount it on the TEST button.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
0: Non Maintained (*)
A: Including test device
*90: 1.5 hour duration
180: 3 hour duration
(*) Non-Maintained operation: The luminaire lights its illumination source, only in power supply's
failure.
Maintained operation: The luminaire lights its illumination source, when it is powered by the mains
power supply or not.
Page 3 from 4
1
2
3
Suspended ceiling
Α-3018 mounting springs
Mounting Easy Light luminaire
in a suspended ceiling
Required
opening in
a suspended
ceiling
Bottom view of a wall
Α-3016 recess
mounting base
Recess mounting for an ''Easy Light"
luminaire in a wall.
340
124
923312017_09_003

Advertisement

loading

This manual is also suitable for:

Easy light gr-310/15lEasy light gr-312/15l