Wiring Thermostat to Communicating Systems

Maximum wire distance between the Daikin One+ and the
»
indoor unit should not exceed 125 feet using 18-gauge wire.
For installing the Daikin Fit outdoor system, it is strongly
»
recommended (for best results) to use 18-gauge wire.
Check for proper voltage before and after wiring
»
is installed.
0.6 VDC between Data 1 and 2
24 VAC between common and power
Wiring communicating indoor unit to communicating
»
outdoor units.
Connect 1, 2, C and R from the Daikin One+, to 1, 2, C
and R at the indoor unit.
Connect wires 1 and 2 from the indoor unit to 1 and 2
at the outdoor unit.
Wiring communicating indoor furnace unit to non-communicating
»
outdoor units.
Connect 1, 2, C and R from the Daikin One+, to 1, 2, C
and R at the indoor furnace unit.
Connect wire Y1 from the indoor furnace unit to Y1 at
the outdoor unit
Under Equipment Setup add '24 VAC Condenser'.
Under '24 VAC Condenser' select the matching kBTU
from 'cool CFM' settings
11