2.2 Installation
Building Technologies
Fire Safety
11
8
13
11
12
1 Back box
2 Battery pack BAT3.6-10
3 Type plate with adhesive label
4 Battery holders
5 Battery connector
6 Housing switching contact
7 Switching unit
8 Stop
not included in the scope of delivery
1
The flashing behavior of the internal alarm indicator is described in document
A6V10401120 in the 'Internal alarm indicator' chapter.
w The back box is fastened.
w You have a new, undamaged battery pack to hand.
w You have key FDMK295 and a Phillips screwdriver to hand.
w The radio gateway has been activated and switched to maintenance mode.
1. Remove the adhesive label with the serial number from the type plate (3) on
the switching unit. Use the adhesive label to mark the position of the radio
manual call point FDM275 on the device location plan.
2. Label the battery pack (2) with the current date.
Mounting and installation
14
15
7
8
9
8
10
11
9 Screws for switching unit
10 Internal alarm indicator
1
11 Plastic/glass insert
12 Housing cover
13 Retainer
14 Spring
15 Triggering device
2
Installation
1
2
5
6
180°
4
3
9
7 | 18
A6V10401114_f_en_--
2018-11-19