Clearances For Installation; System Parameters; Ups Requirements; General Requirements - Toshiba G9000 Specifications

80/100/160/225 kva guide specification three phase uninterruptible power supply
Hide thumbs Also See for G9000:
Table of Contents

Advertisement

Guide Specification – 3-Phase Static Uninterruptible Power Supply

3.2.3 Clearances for installation

Ceiling Level
Front
Bottom
Rear
Sides
Base
4

SYSTEM PARAMETERS

4.1 UPS Requirements:

4.1.1 General Requirements:

Rated Output Capacity
AC/DC Rectifier Type
DC/AC Inverter Type
External Dimensions
Weight
Power Cable Access
Paint Color
4.1.2 AC Input:
Configuration
Rated Voltage
Voltage Variation
Rated Frequency
Frequency Variation
Input Power Factor
80 kVA
100 kVA
160 kVA
225 kVA
80 kVA
100 kVA
160 kVA
225 kVA
: 20" minimum from top of UPS to ceiling
: 40" minimum for maintenance
(Local and regional codes may apply)
: Knockouts for power cable access
: Zero clearance required
: Zero clearance if using bottom cable access
(Standard knockouts for left/right side
cable access )
: Channel mounted
: 80/100/160/225 kVA
(72/90/144/202.5 kW)
: AC/DC multi-level IGBT Rectifier
:DC/AC multi-level IGBT Inverter
Inverter
(W)
(D)
(H)*
: 27.6"x 32.8"x 78.7 (80.6)"
: 27.6"x 32.8"x 78.7 (80.6)"
: 35.4"x 32.8"x 78.7 (80.6)"
: 35.4"x 32.8"x 78.7 (80.6)"
* Unit height with fan assembly installed
: 855 lbs
: 855 lbs
: 1160 lbs
: 1230 lbs
: Bottom, Sides, Top Entry with optional
side cabinet
: Black (Munsell N1.5)
: 3-Phase/3-Wire + Ground
: 480V
: +15% to –20%
: 60Hz
: +/-10%
: Greater than 0.99 lagging at 25%-115% load
7