Optional Receptacle Panel Installation Instructions
these are the instructions for installing the optional modular output receptacle panels for the 1600ep
Series UpS. these instructions apply to all Ue3-rp-XX panel options.
warning: the work outlined in these instructions is to be performed only on a completely un-energized
UpS system.
refer to Figure 1 for location of UpS referenced material. refer to Figure 2 for material referring to the
receptacle panel module.
Step 1: remove the modular receptacle panel cover plate.
on the rear of the UpS, locate the cover plate for the receptacle panel module interface
(see Figure 1).
remove the 6 mounting screws.
remove the cover plate. a square-shaped plug will appear exposed near the upper-left corner
of the uncovered slot.
Step 2: Snap-in output receptacle modular panel
Carefully mate the square-shaped connector on the UpS to its matching counter part on the rear of the
modular panel.
Step 3: mount the receptacle panel
attach the screws removed from the cover plate through the mounting holes of the receptacle panels and
back into the UpS mounting points.
mounting
Screws
Figure 1
1600ep Series instruction manual
Figure 2
45