Operating Precautions - Toshiba 1600EP Series Instruction Manual

Single phase - 3.6-rohs/3.6/6/8/10/14/18/22
Hide thumbs Also See for 1600EP Series:
Table of Contents

Advertisement

Operating Precautions

1.
the UpS should not be powered up until the entire operation manual has been read.
2.
the voltage of the input power source must be within the range of +10% to -30% of the rated
input voltage. the input frequency must be within the rated input frequency range. Voltages and
frequencies outside of the permissible range may activate the internal protection devices.
3.
the UpS should not be used with a load that has a rated input that is greater than the rated
output of the UpS.
4.
Do not use the UpS to provide power to motors that require high starting current or with motors
that require a long starting time, such as vacuum cleaners and machine tools (oversizing the UpS
for lock rotor current would be required).
5.
Do not insert metal objects or combustible materials in the ventilation slots of the UpS.
6.
Do not place, hang, or paste any objects on the exterior surfaces of the UpS.
7.
the capacitors of the UpS maintain a residual charge for a while after turning the UpS off. the
required discharge time for each UpS typeform is provided via a cabinet label and a CHARGE
LED. wait for at least the minimum time indicated on the label and ensure that the CHARGE LED
has gone out before opening the door of the UpS once the UpS power has been turned off.
8.
Do not attempt to disassemble, modify, or repair the UpS. Call your toshiba sales representative
for repair information.
9.
turn the power on only after installing all of the covers.
10.
Do not remove any covers of the UpS when the power is on.
11.
if the UpS should emit smoke, produce an unusual odor, or make sound, turn the power off
immediately.
12.
the heat sink and other components may become extremely hot to the touch. allow the unit to
cool before touching these items.
13.
Warning signs should be placed on or near the load as a notification that the load is being
powered by the UpS.
14.
Additional warnings and notifications shall be posted at the equipment installation location as
deemed required by Qualified Personnel.
WARNING
CAUTION
8
when operating in the inverter mode, placing the
breaker in the OFF position will switch the UpS to
the battery backup mode. the output of the UpS will
continue uninterrupted to the load. the unit must be
in the bypass mode at the time that the breaker is
placed in the OFF position for the UpS to shutdown
power to the load.
wait at least 5 minutes after an emergency power
off (epo) before resetting the UpS breaker. this
allows the UpS circuitry to fully discharge. the UpS
could be damaged if the unit is not fully discharged
before the breaker is reset.
1600ep Series instruction manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents