UPS Connections

Terminal Block
the following illustration is a detail view of the terminal block and wiring connections used for 208/240 volt
units (see
pages
49-50 for terminal block location).
note 1 – if aC input power is 208 Vac rated, short terminals 11 and 12 with a jumper wire. Do not jumper terminal 13 to 12 or 11.
Factory Setting is 208Vac. Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
note 2 – if aC input power is 240 Vac rated, short terminals 12 and 13 with a jumper wire. Do not jumper terminal 11 to 12 or
13. Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
Wire Size and Tightening Torque
Use the following table to select the recommended wire size and terminal lug tightening torque for i/o
wire connections.
terminal
item
number
aC input lines
1 and 2
aC output lines
4, 5, and 7
aC output neutral
6
ground
3 and 8
epo Switch
14 and 15
remote Switch
16 and 17
note: wire size presented as the recommended size followed by a bold number in () that is the maximum wire size
the terminal block can accommodate. See page 48 for knock-out hole sizes on the back of each model.
1600ep Series instruction manual
awg
awg
awg
3.6rohS
3.6 kVa
6 kVa
kVa
12 (8)
12 (8)
(8)
10
12 (8)
12 (8)
(8)
10
(8)
12 (8)
12 (8)
10
12 (8)
12 (8)
(8)
10
16
16
16
16
16
16
awg
awg
awg
8 kVa
10 kVa
14-18 kVa
(1/0)
(1/0)
(1/0)
8
6
4
(1/0)
(1/0)
(1/0)
8
6
4
(1/0)
(1/0)
(1/0)
8
6
4
(1/0)
(1/0)
(1/0)
8
6
4
16
16
16
16
16
16
tightening
awg
torque
22 kVa
lb.-in. (n•m)
(1/0)
14.2 (1.56)
1
(1/0)
14.2 (1.56)
1
(1/0)
14.2 (1.56)
1
(1/0)
14.2 (1.56)
1
16
9.0 (0.99)
16
9.0 (0.99)
11